Appendix A – e-TRIM Modbus Registers
The following list is a description of the relevant Modbus registers in the e-TRIM system. For communications, the e-TRIM supports Modbus on the Host 485 port and ModbusTCP through Ethernet.
|
11 |
Active burner bitmap |
|
14 |
Modbus address |
|
15 |
Master Setpoint (2 decimal places) |
|
16 |
Deviation alarm band setpoint (2 decimal places) |
|
17 |
Out of band alarm delay time |
|
18 |
Alarm disable bitmap |
|
19 |
Alarm bitmap, burners 1 - 16. |
|
20 - 35 |
O2 readings, sensors 1 - 16, 2 decimal places. |
|
68 - 83 |
High Fire ON, sensors 1 - 16. |
|
116 - 131 |
O2 trim delay, sensors 1 - 16. |
|
132 - 147 |
O2 trim interval time, sensors 1 - 16. |
|
148 - 163 |
O2 alarm state, sensors 1 - 16. |
|
|
0 = normal, 1 = bad communications, 2 = out of and pending, 3 = out of band. |
|
164 - 179 |
Alarm delay timer (sec), sensors 1 = 16. |
|
180 - 195 |
O2 offset, sensors 1 - 16. |
|
220 - 235 |
Slave communications status, boards 1 - 16. 0 = bad communications, 4 = OK. |
|
460 |
Critical alarm bitmap |
|
461 - 476 |
Critical alarm, sensors 1 - 16. |
|
477 - 492 |
Critical alarm set point, sensors 1 - 16. |
|
493 |
Critical alarm acknowledge. 1 = acknowledged. |
|
600 |
High fire total time (sec), sensor 1 |
|
601 |
High fire total time (hr), sensor 1 |
|
602 |
Low fire total time (sec), sensor 1 |
|
603 |
Low fire total time (hr), sensor 1 |
|
604 |
High fire timer, sensor 1 |
|
605 |
Low fire timer sensor 1 |
|
606 - 611 |
Timers for Sensor 2 |
|
612 - 617 |
Timers for sensor 3 |
|
618 - 623 |
Timers for sensor 4 |
|
624 - 629 |
Timers for sensor 5 |
|
630 - 635 |
Timers for sensor 6 |
|
636 - 641 |
Timers for sensor 7 |
|
642 - 647 |
Timers for sensor 8 |
|
648 - 653 |
Timers for sensor 9 |
|
654 - 659 |
Timers for sensor 10 |
|
660 - 665 |
Timers for sensor 11 |
|
666 - 671 |
Timers for sensor 12 |
|
672 - 677 |
Timers for sensor 13 |
|
678 - 683 |
Timers for sensor 14 |
|
684 - 689 |
Timers for sensor 15 |
|
690 - 695 |
Timers for sensor 16 |