Appendix A – e-TRIM Modbus Registers

 

The following list is a description of the relevant Modbus registers in the e-TRIM system. For communications, the e-TRIM supports Modbus on the Host 485 port and ModbusTCP through Ethernet.

 

11

Active burner bitmap

14

Modbus address

15

Master Setpoint (2 decimal places)

16

Deviation alarm band setpoint (2 decimal places)

17

Out of band alarm delay time

18

Alarm disable bitmap

19

Alarm bitmap, burners 1 - 16.

20 - 35

O2 readings, sensors 1 - 16, 2 decimal places.

68 - 83

High Fire ON, sensors 1 - 16.

116 - 131

O2 trim delay, sensors 1 - 16.

132 - 147

O2 trim interval time, sensors 1 - 16.

148 - 163

O2 alarm state, sensors 1 - 16.

 

0 = normal, 1 = bad communications, 2 = out of and pending, 3 = out

of band.

164 - 179

Alarm delay timer (sec), sensors 1 = 16.

180 - 195

O2 offset, sensors 1 - 16.

 

220 - 235

Slave communications status, boards 1 - 16. 0 = bad communications, 4 = OK.

460

Critical alarm bitmap

461 - 476

Critical alarm, sensors 1 - 16.

477 - 492

Critical alarm set point, sensors 1 - 16.

493

Critical alarm acknowledge. 1 = acknowledged.

600

High fire total time (sec), sensor 1

601

High fire total time (hr), sensor 1

602

Low fire total time (sec), sensor 1

603

Low fire total time (hr), sensor 1

604

High fire timer, sensor 1

605

Low fire timer sensor 1

606 - 611

Timers for Sensor 2

612 - 617

Timers for sensor 3

618 - 623

Timers for sensor 4

624 - 629

Timers for sensor 5

630 - 635

Timers for sensor 6

636 - 641

Timers for sensor 7

642 - 647

Timers for sensor 8

648 - 653

Timers for sensor 9

654 - 659

Timers for sensor 10

660 - 665

Timers for sensor 11

666 - 671

Timers for sensor 12

672 - 677

Timers for sensor 13

678 - 683

Timers for sensor 14

684 - 689

Timers for sensor 15

690 - 695

Timers for sensor 16