Basic Configuration

      The Basic Configuration page displays current basic parameter values and provides the ability to set, select, and reset values. The parameters are described in more detail below.

      Basic Configuration Web Page

       

      Parameter

      Description

      Set Dat/Time

      Sets the date/time (real time calendar clock).

      Setpoint

      The current flow setpoint.

      Address

      The Modbus address of the device - a number from 1-247. The device will respond to 250 universally.

      Baud Rate

      The baud rate for communications.

      Reset Total

      Resets the totalized value.

      Zero Tare

      Resets the zero flow rate of the meter.

      Max Tare

      Sets the maximum opening position to which the valve is capable of driving.

      Low Flow Alarm

      Triggers an alarm if the flow drops below the programmed value (0 = alarm not set).

      High Flow Alarm

      Triggers an alarm if the flow increases above the programmed value (0 = alarm not set).

      Low Pres Alarm

      Triggers an alarm if the supply pressure drops below the programmed value (0 = alarm not set).

      Deviation Alarm

      Triggers an alarm after 60 seconds if the flow PV deviates from the flow SP more than the defined deviation (0 = alarm not set).

      Under Pressure Alarm**

      Triggers an alarm when the differential pressure is less than 3” W.C. of the supply pressure (On = alarm is active).

      **Not available with a standard eFlo-H or eFlo-L meter.

      Valve Shut Alarm

      Triggers a “Shut” display when the flow is less than 10% of the maximum flow and there is pressure available. This alarm is used mainly on manual eFlo meters and in-line meters to alert the user that the meter’s valve may not be fully closed (On = alarm is active).

      Max Opening Alarm

      Indicates when the valve is opened to its maximum limit (On = alarm is active)

      Parameters and Descriptions for Basic Configuration