-
SSi recommends that the shutoff valve be moved downstream of the meter so that gas pressure on the meter is always available. The error will correct itself when gas pressure is supplied to the meter.
-
Another option is to perform a Zero Calibration. See the Zero Adjustment & Calibration section on page 1 for more details.
Troubleshooting
WARNING!
When troubleshooting, follow all proper safety precautions. Use proper eye protection and hand protection at all times.
|
Problem |
Possible Causes |
Possible Corrective Actions |
---|---|---|
Unit is not reaching higher flow setpoint |
Pressure may be less than pressure specified on order
Meter may not be the correct size
Meter may not be calibrated for correct gas
Gas piping may be too small for required flow
|
Adjust regulator using a manometer to set correct pressure while gas is flowing and meter is open
Call SSi at (513) 772-0060 to discuss a different size (model) of flow meter
Verify Calibration Report for gas calibration. If the gas is different than the gas you are flowing through the meter, contact SSi at (513) 772-0060 to discuss a recalibration.
Verify that the plumbing is adequate for the maximum flow required through the meter. |
Unit is indicating that there is gas flow when no flow should be present |
Zero value is not set on the meter (if gas supply is shut off)
The shutoff valve may be located upstream of the flow meter. This causes a zero drift condition since there is no pressure on the meter. |
Verify that the hand valve for gas supply is closed. If flow is still showing, perform the zero calibration procedure as shown in the manual.
|
Unit is indicating that there is no gas flow when calling for a flow setpoint |
Hand valve for gas supply may be closed
If a solenoid is used, solenoid may not be energized
Restrictions may be present downstream in the gas supply |
Open hand valve.
Ensure that solenoid is energized.
Check for issues such as exhaust gas outlet restriction, and correct any problems. |
Unit indicates that pressure is dropping as flow increases. |
Insufficient gas flow to maintain constant pressure. |
Verify that there is sufficient gas supply to the meter to maintain a constant pressure |
Unit is not communicating |
Communications may not be configured correctly |
Verify RS485 wire polarity
Verify address and baud rate
Verify that only one meter has address set to 1 on the RS485 loop |
Unit is not reaching setpoint |
There may be insufficient gain
Insufficient pressure may be supplied |
Verify gain is high enough; adjust bias as needed
Adjust the pressure to the pressure indicated on the meter and the Calibration Report. Verify the pressure at the high pressure port. |
Setpoint cannot be changed directly from the eFlo control panel |
An analog setpoint signal may be wired and overwriting manual setpoint
A master device wired to the eFlo may be overwriting manual setpoint |
Ensure that an analog input signal to the eFlo is not wired and overwriting manual setpoint
Ensure that no device is actively writing the setpoint via communications |
Troubleshooting
If you experience problems and cannot find the solution after troubleshooting, please call SSi Technical Support at (513) 772-0060.