Specifications
The specifications for the eFlo instrument are as follows.
|
Weight (Including Electronics Housing) |
eFlo-H: 6.2 lb (2.8 kg) eFlo-L: 10.8 lb (4.9 kg) |
|
Power Required |
24 VDC @ 750 mA |
|
Accuracy |
4% |
|
Repeatability |
2% |
|
Turndown Ratio |
6:1 |
|
Medium Temperature Limits |
-10°F to 125°F (-20°C to 51°C) |
|
Ambient Temperature Limits |
-10°F to 125°F (-20°C to 51°C) |
|
Maximum Altitude |
N/A |
|
Flow Output Signal (Linear) |
4-20 mA |
|
Maximum Output Signal Load |
500Ω |
|
Input Control Signal (Linear) |
4-20 mA |
|
Communications |
RS485, Ethernet, USB |
|
Communication Protocol |
Modbus RTU |
|
Pressure Drop @ 100% Capacity
|
1 psi – standard liquid & gas (5 psi optional when required) |
|
Flow Meter Pressure Limits
The pressure will be calibrated to user-specified requirements.
See the Calibration Report included with your product for more details. |
5 psig gas & liquid – minimum allowable 80 psig gas – maximum allowable 50 psig liquid – maximum allowable
|
eFlo-H & eFlo-L Specifications