9.2.4 To Calibrate mA Outputs
Output 3 (808/804) may be supplied as mA outputs. They may be calibrated as follows:-
Connect an ammeter to output 3 – terminals 3A/3B.
In configuration level:-
Operation |
Do This |
Display View |
Additional Notes |
Select the calibration phase |
1. Press or to select ‘PHAS’ |
|
This is found towards the end of the list of ‘P’ codes |
Select low point calibration phase for the mA output to be calibrated (eg OP3) |
2. Press or to select ‘3.NA.L’ |
|
|
Calibrate the low point |
3. Press to select ‘vAL’ 4. Press or to adjust this value so that it reads the same value as shown on the ammeter. For example if the meter reads 2.06 then set the controller reading for 206. The decimal point is not displayed on the controller so that 202 represents 2.02. 5. Press to confirm |
|
|
Select high point calibration phase for the mA output to be calibrated (eg OP3) |
6. Press to go back to ‘PHAS’ 7. Press or to select ‘3.NA.H’ |
|
|
Set the output |
8. Press to select ‘vAL’ 9. Press or to adjust this value so that it reads the same value as shown on the ammeter. The value represents 18.00mA |
|
|
|
10. Press again to confirm and to exit from the calibration phase |
|
|