8.7 Parameter Modbus Addresses
This is a complete list of parameters available in the 800 range, some of which are only available through comms. These addresses are also shown in iTools.
Parameter Mnemonic |
Parameter Name |
Modbus Address Decimal |
||
---|---|---|---|---|
PVInValue |
PV (Temperature) Input Value |
123 |
||
TargetSP |
Target Setpoint. |
NB – do not write continuously changing values to this variable. The memory technology used in this product has a limited number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function or the Alternative Setpoint available over comms (Modbus address 26 )in preference. |
2
|
|
OP |
Manual Output Value (resolution 0.1%, i.e. 50% output = 500) |
130 and 132 |
||
WorkingOP |
Working Output |
4 |
||
WorkingSP |
Working Setpoint (Read Only) |
5 |
||
Pb |
Proportional Band |
6 |
||
Ti |
Integral Time (0 = No Integral Action) |
8 |
||
Td |
Derivative Time (0 = No Derivative Action) |
9 |
||
AL1 |
Alarm 1 Threshold |
13 |
||
AL2 |
Alarm 2 Threshold |
310 |
||
SP.SL |
Active Setpoint Select (0 = Setpoint 1; 1 = Setpoint 2) |
15 |
||
d.bnd |
Channel 2 Deadband |
16 |
||
cb.Lo |
Cutback Low |
17 |
||
cb.Hi |
Cutback High |
18 |
||
r2G |
Relative Cool Gain |
19 |
||
t.st |
Timer Status (0 = Reset; 1 = Run; 2 = Hold; 3 = End) |
23 |
||
SP1 |
Setpoint 1 |
NB – do not write continuously changing values to this variable. The memory technology used in this product has a limited number of write cycles. If ramped setpoints are required, consider using the internal ramp rate function or the Alternative Setpoint (Modbus address 26) in preference. |
138 |
|
SP2 |
Setpoint 2 |
25 |
||
AltSP
|
Alternative setpoint (comms only parameter) may be used as a setpoint or to ramp the setpoint providing a value has been received within a window of about 5 seconds. This may be enabled using the AltSPSelect (address 276). If no value is received then the controller falls back to the currently selected setpoint (SP 1 or SP 2). The Alternative Setpoint may have a local trim (SP Trim, address 27) added to it to compensate for variations in temperature in a particular zone.
This parameter is not saved when the instrument is switched off. It may be written to continuously over communications without risk of damage to the instrument non-volatile memory. |
26 |
||
SPTrim |
Local Trim – added to the remote setpoint to compensate for local temperature variations in a control zone. |
27 |
||
Mr |
Manual Reset |
28 |
||
oP.Hi |
Output High Limit |
30 |
||
oP.Lo |
Output Low Limit |
31 |
||
SP.rr |
Setpoint Rate Limit Value (0 = no rate limit) |
35 |
||
Error |
Calculated Error (PV-SP) |
39 |
||
AL1.H |
Alarm 1 Hysteresis |
47 |
||
AL2.H |
Alarm 2 Hysteresis |
68 |
||
AL3.H |
Alarm 3 Hysteresis |
69 |
||
InstStatus
|
Instrument Status. This is a bitmap: B0 – Alarm 1 Status B1 – Alarm 2 Status B2 – Alarm 3 Status B4 – Auto/Manual Status B5 – Sensor Break Status B6 – Loop Break Status B7 – CT Low load current alarm status B8 – CT High leakage current alarm status B9 – Timer End B10 – PV Over-range (by > 5% of span) B11 – CT Overcurrent alarm status B12 – New Alarm Status B13 – Timer/Ramp Running B14 – Remote (comms) SP Fail B15 – Auto-tune Status In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’. |
75
|
||
InverseStatus |
Inverted Instrument Status. This is an inverted (bitwise) version of the preceding parameter and is provided so that scrolling messages can be triggered when a condition is not active. Bit mappings are as the “Instrument Status”, Modbus address 75 |
76 |
||
InstStatus2 |
Instrument Status 2. This is a bitmap similar to InstStatus and provides a summary of the main instrument status indicators. B0 – EEPROM Write Frequency Warning Flag No further bits are used in the current firmware. |
77 |
||
Ld.A |
Load ON Current |
80 |
||
AL3 |
Alarm 3 Threshold |
177 |
||
HyS |
Ch1 On/Off Hysteresis in Eng Units |
86 |
||
DigIPStatus |
Digital Inputs Status. This is a bitmap: B0 – Not used B1 – Logic input LA B2 – Logic input LB B7 – Power has failed since last alarm acknowledge A value of 1 signifies the input is closed, otherwise it is zero. Values are undefined if options are not fitted or not configured as inputs. |
87 |
||
HyS.C |
Ch2 On/Off Hysteresis in Engineering Units |
88 |
||
FiLt |
Input Filter Time (0 = Off) |
101 |
||
SP.Hi |
Setpoint High Limit |
111 |
||
SP.Lo |
Setpoint Low Limit |
112 |
||
oFS |
PV Offset |
141 |
||
C.Adj |
Calibration Adjust |
146 |
||
IM |
Instrument Mode (0 = Operating mode - all algorithms and I/O are active 1 = Standby - control outputs are off 2 = Config Mode - all outputs are inactive) |
199 |
||
MVInVal |
Input value in millivolts (comms only parameter). |
202 |
||
|
|
|
||
CJCTemp |
CJC Temperature |
215 |
||
SBrk |
Sensor Break Status (0 = Off; 1 = Active) |
258 |
||
NewAlarm |
New Alarm Status (0 = Off; 1 = Active) |
260 |
||
AlLatchStatus |
Alarm Latch |
261 |
||
LoopBreakAlarm |
Loop Break (0 = Off; 1 = Active) |
263 |
||
A.tUn |
Auto-tune Enable (0 = Off; 1 = Enabled) |
270 |
||
A-M |
Mode of the Loop (0 = Auto; 1 = Manual) |
273 |
||
Ac.AL |
Acknowledge all alarms (1 = Acknowledge) |
274 |
||
AltSPSelect |
Alternate Setpoint enable (comms only parameter for the Alternative Setpoint ). |
276 |
||
AltSPPercent |
Alternative setpoint in percent |
277 |
||
AltSPHi |
Alternative input high scalar – sets high range for setpoint input, corresponding to 20mA or 10V depending on the input type. |
278 |
||
AltSPLo |
Alternative input low scalar – sets low range for setpoint input, corresponding to 4mA or 0V depending on the input type. |
279 |
||
AL1Out |
Alarm 1 Status (0 = Off; 1 = Active) |
294 |
||
AL2Out |
Alarm 2 Status (0 = Off; 1 = Active) |
295 |
||
AL3Out |
Alarm 3 Status (0 = Off; 1 = Active) |
296 |
||
Ld.AL |
Low Load Current Threshold |
304 |
||
LE.AL |
High Leakage Current Alarm (0 = Off; 1 = Active) |
305 |
||
Hc.AL |
Over Current Alarm Threshold |
306 |
||
LoadAlarmOut |
Load Alarm Status (0 = Off; 1 = Active) |
307 |
||
LeakAlarmOut |
Leak alarm Status. |
308 |
||
OverAlarmOut |
Over Current alarm Status (0 = Off; 1 = Active) |
309 |
||
Instantaneouscurrent |
Instantaneous current |
311 |
||
SS.SP |
Soft Start Setpoint |
322 |
||
SS.oP |
Soft Start Power Limit |
323 |
||
t.dUr |
Requested Timer Duration |
324 |
||
t.EL |
Elapsed Time |
325 |
||
t.rE |
Time Remaining |
326 |
||
t.thr |
Timer Start threshold |
327 |
||
Unit |
Display Units (0 = Degrees C ; 1 = Degrees F; 3 = None) |
516 |
||
uCAL |
User Calibration Enable (0 = Off; 1 = Lo; 2 = Hi; 3 = Reset) |
533 |
||
DigOPStatus
|
Digital Outputs Status. This is a bitmap: B0 – Output 1 B1 – Output 2 B2 – Output 3 on 808 and 804 controllers B3 – Output 4 It is possible to write to this status word to use the digital outputs in a telemetry output mode. Only outputs whose function is set to ‘none’ are affected, and the setting of any bits in the Digital Output Status word will not affect outputs used for heat (for example) or other functions. Thus it is not necessary to mask in the settings of these bits when writing to this variable. |
551
|
||
AdjustHighOffset |
Adjust High Offset |
560 |
||
AdjustLowOffset |
Adjust Low Offset |
561 |
||
AdjustHighPoint |
Adjust High Point |
562 |
||
AdjustLowPoint |
Adjust Low Point |
563 |
||
Goto |
Select access level |
7935 |
||
P1 |
Input Type and Range |
9001 |
||
P2 |
Decimal Point Position |
9002 |
||
P3 |
Low Scale Range Value |
9003 |
||
P4 |
High Scale Range Value |
9004 |
||
P5 |
Linear Input Low Millivolts |
9005 |
||
P6 |
Linear Input High Millivolts |
9006 |
||
P7 |
Control Output and Type |
9007 |
||
P8 |
Non Linear Cooling Type |
9008 |
||
P11 |
Output 1 Function |
9011 |
||
P12 |
Output 2 Function |
9012 |
||
P13 |
Output 3 Function |
9013 |
||
P14 |
Output 4 Function |
9014 |
||
P15 |
DC Out Range |
9015 |
||
P16 |
Retransmission Initial Scale Value |
9016 |
||
P17 |
Retransmission Full Scale Value |
9017 |
||
P21 |
Alarm 1 Type |
9021 |
||
P22 |
Alarm 1 Latching |
9022 |
||
P23 |
Alarm 1 Blocking |
9023 |
||
P24 |
Alarm 2 Type |
9024 |
||
P25 |
Alarm 2 Latching |
9025 |
||
P26 |
Alarm 2 Blocking |
9026 |
||
P27 |
Alarm 3 Type |
9027 |
||
P28 |
Alarm 3 Latching |
9028 |
||
P29 |
Alarm 3 Blocking |
9029 |
||
P31 |
Current Transformer Source |
9031 |
||
P32 |
Current Transformer Range |
9032 |
||
P33 |
Current Transformer Alarm Latching |
9033 |
||
P34 |
Loop Break Alarm Time |
9034 |
||
P35 |
Sensor Break Alarm Type |
9035 |
||
P36 |
Sensor Break Safe Output Power |
9036 |
||
P37 |
Break Alarms Output |
9037 |
||
P41 |
Timer Configuration |
9041 |
||
P42 |
Timer Resolution |
9042 |
||
P43 |
Timer End Type |
9043 |
||
P44 |
Operative setpoint at start up |
9044 |
||
P51 |
Logic input 1 function |
9051 |
||
P52 |
Logic input 2 function |
9052 |
||
P61 |
Digital communications address |
9061 |
||
P62 |
Digital communications baud rate |
9062 |
||
P63 |
Digital communications parity |
9063 |
||
P64 |
Communications master retransmission parameter |
9064 |
||
P65 |
Communications master retransmission address |
9065 |
||
P71 |
F1 pushbutton functionality |
9071 |
||
P72 |
F2 pushbutton functionality |
9072 |
||
P73 |
Page pushbutton functionality |
9073 |
||
P74 |
Home display second line content |
9074 |
||
P75 |
Home display third line content |
9075 |
||
P76 |
Level 2 passcode |
9076 |
||
P77 |
Configuration level passcode |
9077 |
||
rEc.S |
Recovery point save |
9101 |
||
rEc.L |
Recovery point load |
9102 |
||
PHAS |
Calibration phase |
9103 |
||
Go |
Calibration start |
9104 |
||
vAL |
Calibration analogue output value |
9105 |
||
|
|
|
||
IPAType |
Logic Input 1 channel hardware type (0 = None; 1 = Logic Inputs) |
12352 |
||
IPBType |
Logic Input 2 channel hardware type (808 and 804 only) (0 = None; 1 = Logic Inputs) |
12368 |
||
CommsType |
Digital Communications Module Type (0 = None; 1 = EIA485) |
12544 |
||
CTType |
Current Transformer (0 = None; 1 = CT in) |
12608 |
||
OP1Type |
IO channel 1 hardware type (0 = None; 1 = Relay; 2 = Logic I/O) |
12672 |
||
1.PLS |
IO1 Time proportioning Output minimum pulse time |
12706 |
||
OP2Type |
Output 2 Type (0 = None; 1 = Relay; 2 = Logic; 3 = DC OP [816 only] |
12736 |
||
2.PLS |
Output 2 Time proportioning Output minimum pulse time |
12770 |
||
OP3Type |
Output 3 Type (0 = None; 1 = Relay; 3 = DC OP [808 and 804 only]) |
12800 |
||
3.PLS |
Output 3 Time proportioning Output minimum pulse time |
12834 |
||
OP4Type |
Output 4 Type (0 = None; 1 = Relay) |
13056 |
||
4.PLS |
Output 4 Time proportioning Output minimum pulse time |
13090 |