5.2.6 Output 2

Output 2 is always fitted with a relay (form A) but is disabled by default. The function of the output may be selected from a list of options including heat or cool digital outputs for the control loop, alarms or events.

 

P12

 

Select P12 to configure Output 2 (OP2).

Each output can be used for control, alarms or events as listed below:-

 

The code can be checked against the label on the side of the controller.

nonE

Output disabled (factory default)

Heat

Heat output

 

Output 2 controls the heating power demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs.

 

OP2 State when heating

Relay

Energised

Logic

ON

 

Analogue

On

 

CooL

Cool output

Output 2 controls the cooling demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs.

 

OP2 State when cooling

Relay

Energised

Logic

ON

 

Analogue

On

 

AL1

Alarm 1

Output 2 will operate as shown in the table if the alarm selected is active.

 

Alarm active

AL2

Alarm 2

Relay

Energised

AL3

Alarm 3

Logic

ON

 

Analogue

On

 

AL1. i

Alarm 1 inverted.

Output 2 will operate as shown in the table if the selected alarm is active. This is the normal setting for alarms since if power to the controller fails an alarm state will be indicated by a powered external device.

 

Alarm active

AL2. i

Alarm 2 inverted

Relay

De-energised

AL3. i

Alarm 3 inverted

Logic

OFF

 

Analogue

Off (0mA)

 

t.End

Timer end status

OP2 can be used to operate an external device to indicate when the timer has timed out. A relay is energised and a logic output is ON when the timer has timed out.

 

Timer Operation is described in section 4.11.

t.rUn

Timer run status

OP2 can be used to operate an external device to indicate when the timer is running. A relay is energised and a logic output is ON when the timer is running.