4.3.1 FM 3545 Approval

 

In 816L, 808L and 804L Alarm 2 is permanently assigned to the changeover relay output (OP4). Alarm 2 threshold is protected by a password and cannot be promoted to Level 1 and is, therefore, available in Level 2 only. The password which protects Level 2 access (P76 configuration parameter) cannot assume the 0 value, that is password disabled.

 

The above constraints lock some configuration parameters to fixed values and, therefore, cannot be changed. The following table provides a summary of these parameters, which are also reproduced in the configuration section 5.2.

 

Parameter

Function

Locked value or range

Meaning

P14

Output 4

AL2.i

Output 4 assigned to alarm 2 block with inverted action

P24

Alarm 2 type

Only the Hi and Lo options are available

Alarm 2 is independent of the control set point

P25

Alarm 2 latching

Man

Manual latching, alarm condition must be removed before acknowledgement

P26

Alarm 2 blocking

No

Alarm cannot be ignored during start up

P35

Sensor break alarm type

Lat

A sensor break alarm will be latched

P37

Sensor break alarms output

AL2

A sensor break alarm is assigned to alarm 2

P76

Level 2 pass code

1 – 9999

Level 2 password cannot be disabled

Operating settings AL2

Alarm 2 threshold promotion

Level 2

Alarm 2 threshold is available at Level 2 only

 

These restrictions are active by keyboard and both comms serial interface (i.e. EIA485 and the configuration port) and apply only to FM approved versions. The non-FM approved versions are freely programmable.