13 Appendix B Technical Specification
General |
|||
Environmental performance |
|||
Temperature limits |
Operation: 0 to 55°C (32 to 131°F), |
||
Storage: -20 to 70°C (-4 to 158°F) |
|||
Humidity limits |
Operation: RH: 0 to 90% non-condensing |
||
|
Storage: RH: 5 to 90% non-condensing |
||
Panel sealing |
IP66, NEMA Type 12 |
||
Shock |
10 x 15g pulses |
||
Vibration |
2g peak, 10 to 150Hz |
||
Altitude |
<2000 metres |
||
Atmospheres |
Not suitable for use in explosive or corrosive atmospheres. |
||
Electromagnetic compatibility (EMC) |
|||
Emissions and immunity |
EN61326-1 Suitable for domestic, commercial and light industrial as well as heavy industrial environments. (Class B emissions, Industrial Environment immunity. Low voltage versions are suitable for industrial environments only. |
||
Electrical safety |
|||
(BS EN61010) |
Installation category II; Pollution degree 2 |
||
Installation category II |
The rated impulse voltage for equipment on nominal 230V supply is 2500V |
||
Pollution degree 2 |
Normally only non conductive pollution occurs. Occasionally, however, a temporary conductivity caused by condensation shall be expected. |
||
Physical |
816 |
808 |
804 |
Panel mounting |
1/16 DIN |
1/8 DIN |
1/4 DIN |
Weight grams |
250 |
350 |
420 |
Panel cut-out dimensions mm |
45 x 45 |
45 x 92 |
92 x 92 |
Panel depth |
All 90 mm |
Operator interface |
|
Type |
LED |
Main PV display |
4 digits green |
Secondary display |
4 digits amber |
Third display |
4 digits amber |
Status beacons |
Units, outputs, alarms, active setpoint |
Power requirements |
|
816 |
100 to 230Vac, +/-15% 48 to 62Hz, max 6W
|
808 and 804 |
100 to 230Vac, +/-15% 48 to 62Hz, max 9W
|
Approvals |
|
|
CE, cUL listed (file E57766) Suitable for use in Nadcap and AMS2750D applications under Systems Accuracy Test calibration conditions. Other standards pending. |
Transmitter PSU (not 816) |
|
Isolation |
264Vac double insulated |
Output Voltage |
24Vdc, >28mA, <33mA |
Communications: serial communications option |
|
Protocol |
Modbus RTU client Modbus RTU Host broadcast (1 parameter) |
Isolation |
264Vac double insulated |
Transmission standard |
EIA485 2-wire |
Process Variable Input |
|
Calibration accuracy |
<±0.25% of reading ±1LSD (1) |
Sample rate |
4Hz (250mS) |
Isolation |
264Vac double insulated from the PSU and communications |
Resolution (µV) |
< 0.5µV with a 1.6 second filter |
Resolution (effective bits) |
>17 bits |
Linearisation accuracy |
<0.1% of reading |
Drift with temperature |
<50ppm (typical) <100ppm (worst case) |
Common mode rejection |
48 - 62 Hz, > 120dB |
Series mode rejection |
48 - 62 Hz,> 93dB |
Input impedance |
100MΩ |
Cold junction compensation |
>30 to 1 rejection of ambient temperature |
Cold junction accuracy |
<+1oC at 25oC ambient |
Linear (process) input range |
-10 to 80mV, 0 to 10V with 100KΩ/806Ω external potential divider module |
Thermocouple Types |
K, J, N, R, S, B, L, T, C |
Resistance thermometer Type |
3-wire, Pt100 DIN43760 |
Bulb current |
0.2mA |
Lead compensation |
No error for 22 ohms in all 3 leads |
Input filter |
Off to 59.9 seconds |
Zero offset |
User adjustable over the full display range |
User calibration |
2-point gain & offset |
Notes
(1) Calibration accuracy quoted over full ambient operating range and for all input linearisation types.
OP4 relay |
|
Type |
Form C (changeover) |
Rating |
Min: 100mA @ 12Vdc. Max: 2A @ 264Vac resistive |
Functions |
Control, alarms or events
|
Current Transformer Input |
|
Input current |
0 to 50mA rms 48/62Hz, 10Ω burden resistor fitted inside the module |
Calibration accuracy |
<1% of reading (typical) <4% of reading (worst case) |
Isolation |
By using external CT |
Input impedance |
<20W |
Scale |
10, 25, 50 or 100Amps |
Functions |
Partial load failure, SSR fault |
Digital input (DigIn 1 and 2, Digital Input 2 is not in 816) |
|
Contact |
Contact open >600Ω Contact closed <300Ω |
Input current |
<13mA |
Isolation |
None from PV or system 264Vac double insulated from PSU and communications |
Functions |
Include alarm acknowledge, SP2 select, manual, keylock, timer functions, standby select, RSP select |
Logic Output Channels |
|
Rating |
On/High 12Vdc at <44mA Off/Low <300mV at 100mA |
Isolation |
None from PV or system 264Vac double insulated from PSU and communications |
Functions |
Control, alarms or events |
Relay Output Channels |
|
Type |
Form A (normally open) |
Rating |
Min: 12V, 100mA dc Max: 2A, 264Vac resistive |
Functions |
Control, alarms or events |
Analogue Output Channels (3) (OP3 808 and 804 only) |
|
Rating |
0-20mA into <500W |
Accuracy |
+ (<0.25% of reading + <50μA) |
Resolution |
13.5 bits |
Isolation |
264Vac double insulated |
Functions |
Control, retransmission |
Note (3) Voltage output can be achieved by external adaptor.
Software features |
|
Control |
|
Number of loops |
1 |
Loop update |
250mS |
Control types |
PID, ON/OFF, |
Cooling types |
Linear, fan, oil, water |
Modes |
Auto, manual, standby (Off). |
Overshoot inhibition |
High, low |
Alarms |
|
Number |
3 |
Type |
Absolute high and low, deviation high, low or band |
Latching |
Auto or manual latching, non-latching, event only |
Output assignment |
Up to three conditions can be assigned to one output |
|
|
Other Status Outputs |
|
Functions |
Including sensor break, timer status, loop break, heater diagnostics |
|
|
Timer |
|
Modes |
Dwell when SP reached. Delayed control action Soft start limits power below PV threshold |
Current monitor |
|
Alarm types |
Partial load failure, over current, SSR short circuit, SSR open circuit |
Indication type |
Flashing beacon |
Special features |
|
Features |
Energy monitoring, Recovery point |