9.2 Input Calibration
Calibration can only be carried out in Configuration Level.
If the calibration is not within the specified accuracy follow the procedures in this section:-
In 800 range instruments, inputs which can be calibrated are:-
• mV Input. This is a linear 0 - 80mV range calibrated at two fixed points. This should always be done before calibrating either thermocouple or resistance thermometer inputs. mA range calibration is included in the mV range.
• Thermocouple calibration involves calibrating the temperature offset of the CJC sensor only. Other aspects of thermocouple calibration are also included in mV calibration.
• Resistance Thermometer. This is also carried out at two fixed points - 150Ω and 400Ω.
Before any calibration is attempted, observe the precautions listed in section 9.1.1.