5.2.7 Output 3

Output 3 is available in 808 and 804 only and may be fitted with a relay (form A), or an analogue output depending on the order code. It can be a control or re-transmission output. The function of the output may be selected from a list of options including heat or cool outputs for the control loop, or alarms or events which may be used for external indication.

 

P13

 

Select P13 to configure Output 3 (OP3).

 

Output 3 is not available in model 816.

 

The code can be checked against the label on the side of the controller.

nonE

Output disabled (factory default)

Heat

Heat output

Output 3 controls the heating power demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs.

 

OP3 State when heating

Relay

Energised

 

Analogue

On

 

CooL

Cool output

Output 3 controls the cooling demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs.

 

OP3 State when cooling

Relay

Energised

 

Analogue

On

 

AL1

Alarm 1

Output 3 will operate as shown in the table if the alarm selected is active.

 

Alarm active

AL2

Alarm 2

Relay

Energised

AL3

Alarm 3

 

Analogue

On

 

AL1. i

Alarm 1 inverted.

Output 3 will operate as shown in the table if the selected alarm is active. This is the normal setting for alarms since if power to the controller fails an alarm state will be indicated by a powered external device.

 

Alarm active

AL2. i

Alarm 2 inverted

Relay

De-energised

AL3. i

Alarm 3 inverted

 

Analogue

Off (0mA)

 

SP.rt

SP re-transmission

If OP3 is mA it can be used to transmit an analogue value proportional to the setpoint to an external device.

 

The value is clipped to Low (SP.Lo) and High (SP.Hi) Setpoint limits set in Level 2.

 

oP.rt

OP re-transmission

If OP3 is mA it can be used to transmit an analogue value proportional to the output to an external device.

 

The value of the analogue signal is clipped to the Low (oP.Lo) and High (oP.Hi) output limits set in Level 2.

 

Pv.rt

PV re-transmission

If OP3 is mA it can be used to transmit an analogue value proportional to the process variable to an external device.

 

The value of the analogue signal is clipped to the Low and High scale range set in P codes P3 and P4.

 

t.End

Timer end status

OP3 can be used to operate an external device to indicate when the timer has timed out. A relay is energised when the timer has timed out.

 

Timer Operation is described in section 4.11.

t.rUn

Timer run status

OP3 can be used to operate an external device to indicate when the timer is running. A relay is energised when the timer is running.