5.2.6 Output 2
Output 2 is always fitted with a relay (form A) but is disabled by default. The function of the output may be selected from a list of options including heat or cool digital outputs for the control loop, alarms or events.
P12
|
Select P12 to configure Output 2 (OP2).
Each output can be used for control, alarms or events as listed below:- |
|
The code can be checked against the label on the side of the controller. |
|||
nonE |
Output disabled (factory default) |
|||||
Heat |
Heat output
|
Output 2 controls the heating power demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs. |
|
OP2 State when heating |
||
Relay |
Energised |
|||||
Logic |
ON |
|||||
|
Analogue |
On |
||||
|
||||||
CooL |
Cool output |
Output 2 controls the cooling demand. The sense is set to normal – the state of the output is shown in the table. This is the usual setting for control outputs. |
|
OP2 State when cooling |
||
Relay |
Energised |
|||||
Logic |
ON |
|||||
|
Analogue |
On |
||||
|
||||||
AL1 |
Alarm 1 |
Output 2 will operate as shown in the table if the alarm selected is active. |
|
Alarm active |
||
AL2 |
Alarm 2 |
Relay |
Energised |
|||
AL3 |
Alarm 3 |
Logic |
ON |
|||
|
Analogue |
On |
||||
|
||||||
AL1. i |
Alarm 1 inverted. |
Output 2 will operate as shown in the table if the selected alarm is active. This is the normal setting for alarms since if power to the controller fails an alarm state will be indicated by a powered external device. |
|
Alarm active |
||
AL2. i |
Alarm 2 inverted |
Relay |
De-energised |
|||
AL3. i |
Alarm 3 inverted |
Logic |
OFF |
|||
|
Analogue |
Off (0mA) |
||||
|
||||||
t.End |
Timer end status |
OP2 can be used to operate an external device to indicate when the timer has timed out. A relay is energised and a logic output is ON when the timer has timed out. |
|
Timer Operation is described in section 4.11. |
||
t.rUn |
Timer run status |
OP2 can be used to operate an external device to indicate when the timer is running. A relay is energised and a logic output is ON when the timer is running. |