5.2.2 Analogue Input

P1

Select P1 to configure the Input Type.

Selects the type of sensor connected to the instrument PV input.

 

Input Types and Ranges

Min Range

Max Range

Units

Min Range

Max Range

Units

J.tc

Thermocouple type J

Thermocouples use a linearisation technique to translate from the

raw voltage value produced by the sensor to a temperature

reading on the display.

-210

1200

oC

-346

2192

oF

cA.tc

Thermocouple type K (factory default)

-200

1372

oC

-328

2502

oF

L.tc

Thermocouple type L

-200

900

oC

-328

1652

oF

r.tc

Thermocouple type R

-50

1700

oC

-58

3092

oF

b.tc

Thermocouple type B

0

1820

oC

32

3308

oF

n.tc

Thermocouple type N

-200

1300

oC

-328

2372

oF

t.tc

Thermocouple type T

-200

400

oC

-328

752

oF

S.tc

Thermocouple type S

-50

1768

oC

-58

3215

oF

rtd

Pt100

Platinum Resistance Thermometer (RTD)

-200

850

oC

-328

1562

oF

Nv

-10 to +80mV linear

millivolts

-10.00

80.00

 

 

 

 

0.20

0 - 20mA linear

milliamps require a 2.49W resistor (supplied) across the input terminals.

 

 

 

 

 

 

4.20

4 - 20mA linear

 

 

 

 

 

 

C.tc

Custom downloadable curve.

This requires consulting SSi.