5.2.14.1 Sensor Break Impedance
In some cases the sensor may not immediately break but corrosion may lead to a high impedance condition.
-
For thermocouples a break is indicated if the impedance is greater than about 20KΩ.
-
For a PRT input, sensor break is indicated if any one of the three wires is broken or if the source resistance exceeds about 420Ω or falls below about 15Ω.
-
For mA and volts input sensor break will not be detected due to the load resistor connected across the input terminals.