4.3.1 FM 3545 Approval
In 816L, 808L and 804L Alarm 2 is permanently assigned to the changeover relay output (OP4). Alarm 2 threshold is protected by a password and cannot be promoted to Level 1 and is, therefore, available in Level 2 only. The password which protects Level 2 access (P76 configuration parameter) cannot assume the 0 value, that is password disabled.
The above constraints lock some configuration parameters to fixed values and, therefore, cannot be changed. The following table provides a summary of these parameters, which are also reproduced in the configuration section 5.2.
Parameter |
Function |
Locked value or range |
Meaning |
P14 |
Output 4 |
AL2.i |
Output 4 assigned to alarm 2 block with inverted action |
P24 |
Alarm 2 type |
Only the Hi and Lo options are available |
Alarm 2 is independent of the control set point |
P25 |
Alarm 2 latching |
Man |
Manual latching, alarm condition must be removed before acknowledgement |
P26 |
Alarm 2 blocking |
No |
Alarm cannot be ignored during start up |
P35 |
Sensor break alarm type |
Lat |
A sensor break alarm will be latched |
P37 |
Sensor break alarms output |
AL2 |
A sensor break alarm is assigned to alarm 2 |
P76 |
Level 2 pass code |
1 – 9999 |
Level 2 password cannot be disabled |
Operating settings AL2 |
Alarm 2 threshold promotion |
Level 2 |
Alarm 2 threshold is available at Level 2 only |
These restrictions are active by keyboard and both comms serial interface (i.e. EIA485 and the configuration port) and apply only to FM approved versions. The non-FM approved versions are freely programmable.