TC Trim
The TC Trim Calibration Type will help to apply the correct Cold Junction to the thermocouple input without having the user perform math and determine a Target value.
-
Select the TC Trim Calibration Type.
-
Select the correct input being calibrated in the Inputs field.
-
Sect the correct TC Type and Range (reference Table 1 for the corresponding ranges for each T/C type).
-
Source a temperature to that input.
-
Enter the sourced temperature into the Enter Target field.
-
Push the Calibrate button. A timer will count down from 30 seconds.
-
Once the Calibration Timer has counted down, the corresponding PV 1 or PV 2 value should match the sourced temperature.
Compare the sourced temperature with the corresponding PV 1 or PV 2 value. Make further adjustments as-needed and perform additional calibrations.