Appendix C: Modbus Registers
|
Register |
Description |
|
0 |
firmware version x 100 |
|
1 |
RS232 host port Baud (terms 1,2,& 3) |
|
2 |
RS232 host port; Modbus slave = 1, PGA3500 mode = 2 |
|
3 |
RS485 Slave port Baud (0 to 13 for 1200 to 921600) |
|
4 |
RS485 Slave port; 0 = MMI master, 1 = Modbus master, 9 = Modbus slave, 10 = Modbus listen |
|
5 |
Reserved |
|
6 |
Reserved |
|
7 |
RS485 port Baud (0 to 13 for 1200 to 921600) |
|
8 |
RS485 port; Modbus master = 1, host port = 9 |
|
9 |
Internal Coms baud |
|
10 |
Internal Coms Mode |
|
11 |
RS232 port baud (terms 4,5,& 6) |
|
12 |
RS232 port mode:Modbus slave = 1, Modbus master = 9 |
|
13 |
system mode: 0 = PGA, 1 = MGA, 2 = IR cell |
|
14 |
Modbus address |
|
15 |
degree |
|
16 |
nitriter calculations enable |
|
19 |
trim for the differential pressure |
|
20 |
Item to display 1st on main display |
|
21 |
Item to display 2nd on main display |
|
22 |
Item to display 3rd on main display |
|
23 |
Item to display 4th on main display |
|
24 |
Item to display 5th on main display |
|
25 |
Item to display 6th on main display |
|
33 |
Baud set flag port F |
|
34 |
enable pressure compensation |
|
35 |
pressure trim value |
|
38 |
ratio CO2 CO |
|
39 |
Select CO2 for calulation: 0 = normal IR_gas[2] , 1 = high range IR_gas[4] |
|
40 |
IR Dew point if calculated |
|
41 |
Enable IR Dew point calculation |
|
42 |
IR dew point factor |
|
43 |
Startup pressure reading kPa * 100 |
|
44 |
elevation change from startup in feet * 10 |
|
45 |
Elevation from sea level in feet |
|
46 |
pressure trim value |
|
47 |
Local pressure entered for calibration |
|
48 |
o2 calibration factor (2489 = .2489) |
|
49 |
o2 zero offset |
|
50 |
*50 - 53 Pressure reading at last calibration in kPa * 100 |
|
54 |
Adjust minimum temperature |
|
55 |
Adjust minimum millivolts |
|
56 |
Minimum MV action; 0 = only inhibits adjust and control |
|
57 |
max adjust amount |
|
58 |
maximum COF/PF |
|
59 |
minimum COF/PF |
|
60 |
mode: 0 = monitor, 1 = COF/PF adjust base on %C 2 = COF/PF adjust based on CO |
|
61 |
User input scaled 4-20MA input |
|
62 |
User input zero value (4MA) |
|
63 |
User input span value (20MA) |
|
64 |
flow zero offset |
|
65 |
flow span value |
|
67 |
process factor register |
|
68 |
LED D2 ON time in milliseconds |
|
69 |
LED D2 OFF time in milliseconds |
|
71 |
cal enable |
|
72 |
User input display decimal place |
|
74 |
Web change enable; 0 = disable, 1 = enable |
|
75 |
calibration stage |
|
76 |
Pump ON delay |
|
77 |
Sample OFF delay |
|
78 |
Adjust/control update interval |
|
79 |
sample ON delay time |
|
80 |
H2 zero gas % times 100 (xx.xx) |
|
81 |
H2 span gas % times 100 (xx.xx) |
|
82 |
hydrogen cell calibration request; 1 = zero, 2 = span |
|
83 |
H2 cell in % times 100 (xx.xx) |
|
84 |
System DC Volts |
|
85 |
power state |
|
86 |
HMI State |
|
98 |
Probe ATM Instrument: ; -1 = internal (Input 1 for MV Input 2 for TC), // -2 = internal (Input 1 for MV Input 3 for TC), 0 to Probe_ATM_max for external, use -3 for manual |
|
99 |
Probe temperature instrument: -1 = internal (Input 3 for furn TC), // -2 = internal (Input 2 for furn TC), 0 to Probe_TC_max for external, use -3 for manual |
|
100 |
local cooler ON set point |
|
101 |
local cooler OFF set point |
|
102
|
auto calibration and/or sequencing bit 0 = auto cal; 0 = OFF, 1 = ON bit 1 = sequencing; 0 = OFF, 1 = ON bit 2 = seq mode; 0 = normal; 1 = specific bits 4 - 7 N.U. bits 8 - 13 CH active bit map bits 14 - 15 N.U. |
|
103 |
Auto cal interval in minutes 0 = OFF |
|
104 |
Auto Zero interval in minutes 0 = OFF |
|
105 |
Auto data display time at end of seq |
|
106 |
purge time before cal or zero |
|
107 |
if auto cal is avail this is 1 |
|
108 |
Auxiliary relays output desired states |
|
109 |
relays output desired states // 0 = pump, 1 = Alarm 2, 2 = Alarm 1, 3 = Aux cal gas // 4 = Sample, 5 = ACZ zero gas, 6 = ACZ span gas, 7 = AC/cooler ON |
|
110 |
Selected gas type; 0 = none |
|
111 |
Reading for gas 1 |
|
112 |
Full scale range for gas 1 |
|
113 |
Decimal place location; low byte = display, hi = source |
|
114 |
Span gas value for gas 1 |
|
115 |
see above |
|
116 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
120 |
Selected gas type; 0 = none |
|
121 |
Reading for gas 2 |
|
122 |
Full scale range for gas 2 |
|
123 |
Decimal place location; low byte = display, hi = source |
|
124 |
Span gas value for gas 2 |
|
125 |
see above |
|
126 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
130 |
Selected gas type; 0 = none |
|
131 |
Reading for gas 3 |
|
132 |
Full scale range for gas 3 |
|
133 |
Decimal place location; low byte = display, hi = source |
|
134 |
Span gas value for gas 3 |
|
135 |
see above |
|
136 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
140 |
Selected gas type; 0 = none |
|
141 |
Reading for gas 4 |
|
142 |
Full scale range for gas 4 |
|
143 |
Decimal place location; low byte = display, hi = source |
|
144 |
Span gas value for gas 4 |
|
145 |
see above |
|
146 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
150 |
Selected gas type; 0 = none |
|
151 |
Reading for gas 5 |
|
152 |
Full scale range for gas 5 |
|
153 |
Decimal place location; low byte = display, hi = source |
|
154 |
Span gas value for gas 5 |
|
155 |
see above |
|
156 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
160 |
Selected gas type; 0 = none |
|
161 |
Reading for gas 6 |
|
162 |
Full scale range for gas 6 |
|
163 |
Decimal place location; low byte = display, hi = source |
|
164 |
Span gas value for gas 6 |
|
165 |
see above |
|
166 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
170 |
Calculated value type type; 0 = none |
|
171 |
Reading for CV 1 |
|
172 |
Full scale range for CV 1 |
|
173 |
Decimal place location; low byte = display, hi = source |
|
174 |
Zero Scale value for CV 1 |
|
175 |
see above |
|
176 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
180 |
Calculated value type type; 0 = none |
|
181 |
Reading for CV 2 |
|
182 |
Full scale range for CV 2 |
|
183 |
Decimal place location; low byte = display, hi = source |
|
184 |
Zero Scale value for CV 2 |
|
185 |
see above |
|
186 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
190 |
Calculated value type type; 0 = none |
|
191 |
Reading for CV 3 |
|
192 |
Full scale range for CV 3 |
|
193 |
Decimal place location; low byte = display, hi = source |
|
194 |
Zero Scale value for CV 3 |
|
195 |
see above |
|
196 |
0 = blank, 1 = %, 2 = deg F, 3 = deg C, |
|
197 |
low alarm limit |
|
198 |
high alarm limit |
|
199 |
high range % CO2 x100 |
|
200 |
% CO x100 |
|
201 |
%CO2 x10000 |
|
202 |
%O2 x10 |
|
203 |
%CH4 x100 |
|
204 |
Turn off bench, pump, and sample |
|
205 |
IR %C |
|
206 |
IR suggested COF |
|
207 |
IR suggested PF |
|
208 |
IR equivalent millivolts |
|
209 |
probe MV |
|
210 |
probe COF |
|
211 |
probe temperature |
|
212 |
probe process factor |
|
213 |
probe %C |
|
214 |
pump run minutes |
|
215 |
pump run weeks |
|
216 |
pump status |
|
217 |
pump run now |
|
218 |
pump run max |
|
219 |
calibration status |
|
220 |
IR temperature |
|
221 |
control output in percent |
|
222 |
sample flow |
|
223 |
sample valve state |
|
224 |
sample valve control |
|
225 |
flow timer |
|
226
|
Status of base; 0 = OFF, 1 = pump delay ON 2 = sample delay, 3 = measure delay 4 = delay OFF, 5 = ON |
|
227
|
alarm bit map bit 0 = low flow; bit 1 = base communications bit 2 = max factor; bit 3 = min factor; bit 4 = PC_comp alarm ; bit 5 = auto cal alarm bit 6 = programmer alarm; bit 7 thru 15 = gas alarms. high byte is acknowledge |
|
228 |
alarm bit map 2: bit 0 = FC TC; Bit 1 = PB TC bit 2 = PB MV; bit 3 = PB COF/PF bit 4 = PB %C; bit 5 = ambient temperature bit 6 = gas temperature bit 7 thru 15 not assigned. |
|
229 |
alarm 1 assignment bit mask 0 = not assigned; 1 = assigned |
|
230 |
alarm 2 assignment bit mask 0 = not assigned; 1 = assigned bits 0 to 6 are alarm_bit_map1 bits (0 to 6) bits 7 to 15 are alarm_bit_map bits (7 to 15) alarm_bit_map bits 0 to 6 are always alarm 1 |
|
231 |
local temperature x 10 in deg F or C based on degree |
|
236 |
pressure data difference |
|
237 |
number of entries in Que |
|
238 |
pressure reading in kPa * 100 |
|
239 |
pressure difference due to elevation in kPa * 100 |
|
240 |
sea level (barometric) pressure |
|
241 |
pressure in atmospheres * 1000 |
|
242 |
pressure in inHG * 100 |
|
243 |
external temperature x 10 in deg F or C based on degree |
|
244 |
external oxygen data from O2 instrument |
|
246 |
H2 cell communications status |
|
247 |
UB check result |
|
248 |
pressure sensor and calculation select; bits 0 to 3 = gage; 0000 = Std 36.3 PSI, 0001 = SS 50 PSI bits 4 to 7 = calculation; 0000 = on board absolute, 0001 = SPUD differential |
|
249 |
pressure diff upstream to downstream in kPa * 100 |
|
250 |
Slave inst Type |
|
251 |
Slave Inst Port |
|
252 |
Slave inst address |
|
514 |
year |
|
515 |
month |
|
516 |
day |
|
517 |
day of week |
|
518 |
hour |
|
519 |
min |
|
520 |
sec |
|
530 |
Slave Coms Status |
|
610 |
IR cell seq flag |
|
611 |
IR calibration requests |
|
612 |
calibration mode |
|
613 |
calibration timer for purge, etc |
|
614 |
calibration counter |
|
615 |
calibration enable CO |
|
616 |
calibration enable CO2 |
|
617 |
calibration enable CH4 |
|
618 |
calibration enable CO2H |
|
620 |
calibration alarm bit map |
|
640 |
calibration span gas 1 |
|
641 |
calibration span gas 2 |
|
642 |
calibration span gas 3 |
|
643 |
calibration span gas 4 |
|
644 |
calibration span gas 5 |
|
645 |
auto calibration span gas 2 |
|
646 |
auto calibration span gas 3 |
|
647 |
auto calibration span gas 4 |
|
648 |
auto calibration span gas 5 |
|
649 |
aux calibration span gas 2 |
|
650 |
aux calibration span gas 3 |
|
651 |
aux calibration span gas 4 |
|
652 |
aux calibration span gas 5 |
|
653 |
sample calibration span gas 2 |
|
654 |
sample calibration span gas 3 |
|
655 |
sample calibration span gas 4 |
|
656 |
sample calibration span gas 5 |
|
657 |
calibration gas source; 0 = auto, 1 = aux, 2 = sample with pump, 3 = sample w/o pump |
|
666 |
internal use |
|
667 |
internal use |
|
668 |
ambient temperature trim; deg C * 100 |
|
669 |
gas (cell) temperature trim; deg C * 100 |
|
680 |
AIB Desired IN 1 Type |
|
681 |
Desired IN 2 Type |
|
682 |
Desired IN 3 Type |
|
683 |
Desired IN 4 Type |
|
684 |
Desired IN 5 Type |
|
685 |
cal enable |
|
686 |
CJ cal or zero/span voltage cal |
|
687 |
Calibration Range register. Sets the voltage gain for a calibration. |
|
688 |
bitmap of channels to be calibrated |
|
689 |
Calibration value |
|
690 |
AIBA Desired IN 1 Type |
|
691 |
Desired IN 2 Type |
|
692 |
Desired IN 3 Type |
|
693 |
Desired IN 4 Type |
|
694 |
Desired IN 5 Type |
|
695 |
cal enable |
|
696 |
CJ cal or zero/span voltage cal |
|
697 |
Calibration Range register. Sets the voltage gain for a calibration |
|
698 |
bitmap of channels to be calibrated |
|
699 |
Calibration value |
|
700 |
Gas Calorific Value x100 xx.xx |
|
701 |
Gas Calorific Value factor for CO x1000 xx.xxx |
|
702 |
Gas Calorific Value factor for CH4 x100 xx.xx |
|
703 |
Gas Calorific Value factor for H2 x1000 xx.xxx |
|
708 |
Kc CH4 |
|
709 |
Kc Boudouard |
|
710 |
indicates that co data is valid |
|
711 |
indicates that co2 data is valid |
|
712 |
indicates that ch4 data is valid |
|
713 |
High CO2 data valid |
|
720 |
initiate carb Calc |
|
721 |
alloy factor for calculation 10000 = 1.0000 |
|
722 |
default Hydrogen to use if no H2 cell 40% = 40.00 |
|
723 |
Surface carbon activity |
|
724 |
Carbon with alloy factor = 1 |
|
725 |
Carbon with specified alloy factor |
|
726 |
carbon calculated from only CO and CO2 with alloy factor = 1 |
|
727 |
carbon calculated from only CO and CO2 with supplied alloy factor |
|
728 |
IR %C based on original 3 gas calculation |
|
729 |
carb calc mode |
|
730 |
IR factor mode; 0 = original factor, 1 = External factor, 2 = default table lookup, 3 = eternal table look up |
|
731 |
IR shim factor |
|
732 |
Pressure compensation factor; 0 = off, 10 = 1.0, max 2.0 |
|
733 |
CH4 factor |
|
734 |
IR CO compensation factor |
|
735 |
IR shim factor, working value |
|
736 |
CH4 factor, working value |
|
737 |
IR shim factor, External value |
|
738 |
CH4 factor, External value |
|
739 |
Calculation flag 0 = COF, 1 = Process Factor |
|
740 |
pump ON delay timer |
|
741 |
sample OFF delay timer |
|
742 |
sample ON delay timer |
|
743 |
interval timer for COF/PF adjust |
|
744 |
pump mode; 0 = off, 1 = on, 2 = auto |
|
750 |
Dac 1 assignment |
|
751 |
Dac 2 assignment |
|
752 |
Dac 3 assignment |
|
753 |
Dac 4 assignment |
|
754 |
Dac 1 zero |
|
755 |
Dac 1 span |
|
756 |
Dac 2 zero |
|
757 |
Dac 2 span |
|
758 |
Dac 3 zero |
|
759 |
Dac 3 span |
|
760 |
Dac 4 zero |
|
761 |
Dac 4 span |
|
770 |
furnace TC Low alarm limit |
|
771 |
furnace TC High alarm limit |
|
772 |
probe TC Low alarm limit |
|
773 |
probe TC High alarm limit |
|
774 |
probe MV Low alarm limit |
|
775 |
probe MV High alarm limit |
|
776 |
probe COF/PF Low alarm limit |
|
777 |
probe COF/PF High alarm limit |
|
778 |
probe %C Low alarm limit |
|
779 |
probe %C High alarm limit |
|
780 |
Ambient temperature Low alarm limit |
|
781 |
Ambient temperature High alarm limit |
|
782 |
Ambient temperature Low alarm limit |
|
783 |
Ambient temperature High alarm limit |
|
800 |
Gas1/Gas2 ratio |
|
820 |
HiTech CO compensation ratio * 1000 |
|
821 |
HiTech CO2 compensation ratio * 1000 |
|
822 |
HiTech CH4 compensation ratio * 1000 |
|
825 |
Calculated new factor for COF/PF adjust |
|
826 |
pump control; 0 = off, 1 = on |
|
828 |
Bit 0 = CO Alarm Armed, Bit 1 = CO Alarm Alarm, Bit 2 = CO2 Alarm Armed, Bit 3 = CO2 Alarm Alarm, Bit 4 = CH4 Alarm Armed, Bit 5 = CH4 Alarm Alarm, Bit 6 = IR PC Alarm Armed, Bit 7 = IR PC Alarm Alarm |
|
829 |
Bits 0 - 1 CO Alarm Bits 2 - 3 CO2 alarm, Bits 4 - 5 CH4 alarm, Bits 6 -7 IR PC alarm 00 = OFF, 01 = armed, 10 = timing, 11 = alarm |
|
830 |
CO alarm type bits 0 - 1; 0 = off, 1 = band, 2 = dev bit 2 N/A bit 3 N/A control bits; bit 8 = armed, bit 9 = safe, bit 10 = timing, bit 11 = alarm bits 13 to 15 NU |
|
831 |
CO alarm set point |
|
832 |
CO alarm hysteresis |
|
833 |
CO Minimum temperature for active alarm |
|
834 |
CO Maximum temperature for active alarm |
|
835 |
CO on delay time in seconds |
|
836 |
CO center point for deviation and band alarms |
|
837 |
CO alarm timer |
|
840 |
CO2 alarm type bits 0 - 1; 0 = off, 1 = band, 2 = dev bit 2 N/A bit 3 N/A control bits; bit 8 = armed, bit 9 = safe, bit 10 = timing, bit 11 = alarm bits 13 to 15 NU |
|
841 |
CO2 alarm set point |
|
842 |
CO2 alarm hysteresis |
|
843 |
CO2 Minimum temperature for active alarm |
|
844 |
CO2 Maximum temperature for active alarm |
|
845 |
CO2 on delay time in seconds |
|
846 |
CO2 center point for deviation and band alarms |
|
847 |
CO2 alarm timer |
|
850 |
CH4 alarm type bits 0 - 1; 0 = off, 1 = band, 2 = dev bit 2 N/A bit 3 N/A control bits; bit 8 = armed, bit 9 = safe, bit 10 = timing, bit 11 = alarm bits 13 to 15 NU |
|
851 |
CH4 alarm set point |
|
852 |
CH4 alarm hysteresis |
|
853 |
CH4 Minimum temperature for active alarm |
|
854 |
CH4 Maximum temperature for active alarm |
|
855 |
CH4 on delay time in seconds |
|
856 |
CH4 center point for deviation and band alarms |
|
857 |
CH4 alarm timer |
|
860 |
%C alarm type bits 0 - 1; 0 = off, 1 = band, 2 = dev bit 2 N/A bit 3 N/A control bits; bit 8 = armed, bit 9 = safe, bit 10 = timing, bit 11 = alarm bits 13 to 15 NU |
|
861 |
%C alarm set point |
|
862 |
%C alarm hysteresis |
|
863 |
%C Minimum temperature for active alarm |
|
864 |
%C Maximum temperature for active alarm |
|
865 |
%C on delay time in seconds |
|
866 |
%C center point for deviation and band alarms |
|
867 |
%C alarm timer |
|
897 |
O2 cal span value %O2 x 10 |
|
898 |
O2 calibration req; 1 = zero, 2 = span |
|
899 |
return code of UDPDL init() |
|
900 |
product ID code |
|
901 |
reset logging |
|
902 |
Dynamic C compiler version in hex |
|
903 |
long date/time stamp in secs from |
|
904 |
midnight Jan 1, 1980. |
|
905 |
Hack attempts counter |
|
906 |
Web access code, level 1 |
|
907 |
Web access code, level 2 |
|
908 |
session ID passed to Java Applet |
|
909 |
internal use |
|
910
|
Force user block write; 0xa5 (165) = write w/o conf, 0xa9 (169) = write with config, 222 = write user setups, 444 = read user setups |
|
914 |
4 locations for IP address (14 - 17) |
|
918 |
4 locations for net mask (18 - 21) |
|
922 |
4 locations for gateway (22 - 25) |
|
930 |
10 locations for port states |
|
940 |
auto calibration interval timer |
|
941 |
auto zero interval timer |
|
942 |
auto cal/zero request; bit 0 = zero, bit 1 = span |
|
943 |
auto cal/zero sequence |
|
944 |
sequence timer |
|
945 |
auto cal/zero status |
|
946 |
Flag to initiate log of Auto cal |
|
947 |
Number of entries in Auto cal log file |
|
980 |
4 locations for Time server IP address |
|
984 |
UTC time zone as a quarter hour offset from UTC must be +/- 100 For EST with a -5 hour difference enter -20 |
|
985 |
UTC update interval in days (0 to 399) 0 disables |
|
986 |
UTC update flag |
|
987 |
UTC result |
|
996 |
web page writes here as update indicator |
|
1000-1099 |
atmosphere instrument |
|
1100-1199 |
temperature instrument |
|
1200-1299 |
spare instrument slot |
|
1311 |
%H2 x100 |
|
1325 |
offset in H2_DACbase for first DAQ board/ DAC status = copy of COM_stat_X |
|
1326 |
board address (lo Byte)/ baud rate; 0 = 9600, 1 = 19200 (hi Byte) |
|
1327 |
DAC 0 zero calibration |
|
1328 |
DAC 0 span calibration |
|
1329 |
DAC 1 zero calibration |
|
1330 |
DAC 1 span calibration |
|
1331 |
DAC 2 zero calibration |
|
1332 |
DAC 2 span calibration |
|
1333 |
DAC 3 zero calibration |
|
1334 |
DAC 3 zero calibration |
|
1335 |
DAC 0 value |
|
1336 |
DAC 1 value |
|
1337 |
DAC 2 value |
|
1338 |
DAC 3 value |
|
1339 |
DAC version |
|
1345 |
DAC Out 0 |
|
1346 |
DAC Out 1 |
|
1347 |
DAC Out 2 |
|
1348 |
DAC Out 3 |
|
1350 |
offset in H2_DACbase for second DAQ board/ DAC status = copy of COM_stat_X |
|
1351 |
board address (lo Byte)/ baud rate; 0 = 9600, 1 = 19200 (hi Byte) |
|
1352 |
DAC2 0 zero calibration |
|
1353 |
DAC2 0 span calibration |
|
1354 |
DAC2 1 zero calibration |
|
1355 |
DAC2 1 span calibration |
|
1356 |
DAC2 2 zero calibration |
|
1357 |
DAC2 2 span calibration |
|
1358 |
DAC2 3 zero calibration |
|
1359 |
DAC2 3 span calibration |
|
1360 |
DAC2 0 value |
|
1361 |
DAC2 1 value |
|
1362 |
DAC2 2 value |
|
1363 |
DAC2 3 value |
|
1364 |
DAC2 version |
|
1370 |
DAC2 Out 0 |
|
1371 |
DAC2 Out 1 |
|
1372 |
DAC2 Out 2 |
|
1373 |
DAC2 Out 3 |
|
1400 |
Smart Power Sense Relay Board version number |
|
1401 |
RS232: Determines mode: modbus slave = 0, modbus master = 1 |
|
1402 |
RS232: Values are from 0 to 2. 0 = 9600, 1 = 19200, 2 = 38400 |
|
1403 |
RS485: Determines mode: modbus slave = 0, modbus master = 1 |
|
1404 |
RS485: Values are from 0 to 2. 0 = 9600, 1 = 19200, 2 = 38400 |
|
1405 |
Temperature trim for thermistor 1 |
|
1406 |
A/D counts for thermistor 1 |
|
1407 |
thermistor 1 temperature |
|
1408 |
%O2 A/D counts |
|
1409 |
AIN 1 A/D counts |
|
1410 |
AIN 2 A/D counts |
|
1411 |
AIN 3 A/D counts |
|
1412 |
Voltage monitor counts |
|
1413 |
Relay outputs |
|
1414 |
Board modbus address (important for slave only) |
|
1415 |
Model number Map as reg 900 |
|
1416 |
internal use SFD |
|
1417 |
DC Volts calculated from VMonitorCounts |
|
1418 |
Power status for orderly shut down |
|
1419 |
Power Control which way are we going. |
|
1420 |
Power Timer |
|
1421 |
Power Relays; bit 0 is HMI, Bit 1 is other Electronics |
|
1422 |
SPUD System mode; 0 = plain Jane, 1 = H2, 2 = SDS |
|
1423 |
Pump active (ON); 0 = no, 1 = yes |
|
1424 |
Pump request; 0 = OFF, 1 = ON |
|
1425 |
Pump flow measured |
|
1426 |
Pump flow setpoint (0 to 1000) |
|
1427 |
digital inputs active low |
|
1428 |
Survey points |
|
1429 |
degree |
|
1430 |
timer for the SDS module |
|
1431 |
Internal use |
|
1432 |
Battery voltage counts |
|
1433 |
Battery voltage |
|
1434 |
DC voltage counts |
|
1435 |
DC voltage |
|
1436 |
Temperature trim for thermistor 2 |
|
1437 |
A/D counts for thermistor 2 |
|
1438 |
thermistor 2 temperature |
|
1440 |
digital inputs active High bit 0 = COF/PF inhibit, bit 1 = pump stop, bit 2, = auto zero, bit 3 = auto span |
|
1451 |
Smart AIB current version number of the firmware |
|
1452 |
0 = °F, 1 = °C, 2 = °R, 3 = K |
|
1453 |
Cold Junction Temperature |
|
1458 |
Input type |
|
1463 |
Process Variable |
|
1468 |
enables a calibration |
|
1469 |
CJ cal or zero/span voltage cal |
|
1470 |
Calibration Range register. Sets the voltage gain for a calibration. |
|
1471 |
bitmap of channels to be calibrated |
|
1472 |
First of 5 Calibration value |
|
1477 |
First of 5 calibration timers |
|
1482 |
0 = no calibration, 1 = calibration in progress |
|
1483 |
First of 5 calibration error calculations |
|
1487 |
End of calibration registers |
|
1488 |
First of 5 Scaled VDC |
|
1498 |
message update flag |
|
1499 |
calculation sequence |
|
1500 |
Com status message 1 |
|
1504 |
Com status message 2 |
|
1516 |
A/D 1 status register (negative) |
|
1517 |
A/D 1 reading on |
|
1519 |
A/D 1 status register (positive) |
|
1520 |
A/D 1 reading off |
|
1522 |
A/D 2 status register (negative) |
|
1523 |
A/D 2 reading on |
|
1525 |
A/D 2 status register (positive) |
|
1526 |
A/D 2 reading off |
|
1528 |
A/D 3 status register (negative) |
|
1529 |
A/D 3 reading on |
|
1531 |
A/D 3 status register (positive) |
|
1532 |
A/D 3 reading off |
|
1534 |
A/D 4 status register (negative) |
|
1535 |
A/D 4 reading on |
|
1537 |
A/D 4 status register (positive) |
|
1538 |
A/D 4 reading off |
|
1540 |
IR trigger time |
|
1541 |
time from off to on |
|
1542 |
A/D selector |
|
1543 |
ambient temperature raw counts (10 bits resolution) |
|
1544 |
ambient temperature trim |
|
1545 |
gas temperature raw counts (10 bits resolution) |
|
1546 |
gas temperature trim |
|
1547 |
absolute pressure raw counts (10 bits resolution) |
|
1548 |
absolute pressure trim |
|
1549 |
differential pressure raw counts (10 bits resolution) |
|
1550 |
differential pressure trim |
|
1551 |
digital status word |
|
1552 |
Baud Rate selection variable |
|
1600 |
Block Gas 1 value |
|
1601 |
Block Gas 2 value |
|
1602 |
Block Gas 3 value |
|
1603 |
Block Gas 4 value |
|
1604 |
Block Gas 5 value |
|
1605 |
Block Gas 6 value |
|
1606 |
Block Calculated Value 1 |
|
1607 |
Block Calculated Value 2 |
|
1608 |
Block Calculated Value 3 |
|
1609 |
Block IR %C |
|
1610 |
Block IR suggested COF |
|
1611 |
Block IR suggested PF |
|
1612 |
Block IR equivalent millivolts |
|
1613 |
Block probe MV |
|
1614 |
Block probe COF |
|
1615 |
Block probe temperature |
|
1616 |
Block probe process factor |
|
1617 |
Block probe %C |
|
1618 |
Block IR temperature |
|
1619 |
Block sample flow |
|
1620 |
Block alarm bit map |
|
1621 |
Block mode: 0 = monitor, 1 = COF/PF adjust base on %C, 2 = COF/PF adjust based on CO |
|
1622 |
Block auto cal/zero sequence |
|
1623 |
Block auto cal/zero status |
|
1628 |
Block Request for pump mode; 0 = no request, 1, 2, & 3 = 0, 1,2 in pump_mode |
|
1629 |
Block Request for IR mode; 0 = no request, 1, 2, & 3 = 0, 1,2 in IR_mode |
|
1650 |
Block W Gas 1 value |
|
1651 |
Block W Gas 2 value |
|
1652 |
Block W Gas 3 value |
|
1653 |
Block W Gas 4 value |
|
1654 |
Block W Gas 5 value |
|
1655 |
Block W Gas 6 value |
|
1656 |
Block W Calculated Value 1 |
|
1657 |
Block W Calculated Value 2 |
|
1658 |
Block W Calculated Value 3 |
|
1659 |
Block W IR %C |
|
1660 |
Block W IR suggested COF |
|
1661 |
Block W IR suggested PF |
|
1662 |
Block W IR equivalent millivolts |
|
1663 |
Block W probe MV |
|
1664 |
Block W probe COF |
|
1665 |
Block W probe temperature |
|
1666 |
Block W probe process factor |
|
1667 |
Block W probe %C |
|
1668 |
Block W IR temperature |
|
1669 |
Block W sample flow |
|
1670 |
Block W alarm bit map |
|
1671 |
Block W mode: 0 = monitor, 1 = COF/PF adjust base on %C, 2 = COF/PF adjust based on CO |
|
1672 |
Block W auto cal/zero sequence |
|
1673 |
Block W auto cal/zero status |
|
1699 |
Block Write Timer |
|
1704 |
Digital Output 1 setpoint |
|
1705 |
Digital Output 1 actual |
|
1706 |
Digital 1 Input |
|
1714 |
Digital Output 2 setpoint |
|
1715 |
Digital Output 2 actual |
|
1716 |
Digital 2 Input |
|
1724 |
Digital Output 3 setpoint |
|
1725 |
Digital Output 3 actual |
|
1726 |
Digital 3 Input |
|
1799 |
Set Point register |
|
1801 |
Flow Meter 1 Flow |
|
1803 |
Flow Meter 1 Set Point |
|
1811 |
Flow Meter 2 Flow |
|
1813 |
Flow Meter 2 Set Point |
|
1821 |
Flow Meter 3 Flow |
|
1823 |
Flow Meter 3 Set Point |
|
1831 |
Flow Meter 4 Flow |
|
1833 |
Flow Meter 4 Set Point |
|
1841 |
Flow Meter 5 Flow |
|
1843 |
Flow Meter 5 Set Point |
|
1851 |
Flow Meter 6 Flow |
|
1853 |
Flow Meter 6 Set Point |
|
1861 |
Flow Meter 7 Flow |
|
1863 |
Flow Meter 7 Set Point |
|
1871 |
Flow Meter 8 Flow |
|
1873 |
Flow Meter 8 Set Point |
|
8900 |
ambient tempserature; deg F x 100 |
|
8901 |
gas (cell) temperature, deg F x 100 |
|
8902 |
cell abs pressure |
|
8903 |
cell differential pressure |
|
8904 |
gas 1 peak to peak (first of 5) |
|
8909 |
gas 1 level at zero (N2) (first of 5) |
|
8914 |
gas 1 gain constant from span (first of 5) |
|
8919 |
gas 1 reading with compensation (first of 5) |
|
8924 |
gas 1 value (first of 5) |
|
8929 |
gas 1 pos (first of 5) |
|
8934 |
gas 1 neg (first of 5) |
|
8939 |
gas 1 value with TC adjust (first of 5) |
|
8944 |
gas 1 value with press adjust (first of 5) |
|
8949 |
gas 1 value with both (first of 5) |
|
8954 |
temperature ratio Tcal/T (first of 5) |
|
8959 |
pressure ratio P/Pcal (first of 5) |
|
8964 |
filter time in MS (first of 5) |
|
8969 |
Integer of calibration average (first of 5) |
|
8974 |
Integer of gas read at ave (first of 5) |
|
8989 |
Ambient temperature pre-trim |
|
8990 |
Gas temperature pre-trim |
|
8991 |
Normalized Absorbance (CH4) |
|
8992 |
Normalized Absorbance (CO2) |
|
8993 |
Normalized Absorbance (CO) |
|
8994 |
Normalized Absorbance (CO2 -h) |
|
8995 |
gas 1 p2p raw |
|
9100 |
Gas 1 Name |
|
9110 |
Gas 2 Name |
|
9120 |
Gas 3 Name |
|
9130 |
Gas 4 Name |
|
9140 |
Gas 5 Name |
|
9150 |
Gas 6 Name |
|
9160 |
Calculated Value 1 Name |
|
9170 |
Calculated Value 2 Name |
|
9180 |
Calculated Value 3 Name |
|
9191 |
Queue 1 Status |
|
9192 |
Queue 2 Status |
|
9193 |
Queue 3 Status |
|
9194 |
Queue 4 Status |
|
9195 |
Queue 5 Status |
|
9196 |
Queue 6 Status |
|
9197 |
Queue Instrument Number |
|
9198 |
Queue Register |
|
9199 |
Queue Data |
|
19800 |
IR factor default ATM setpoint 1 |
|
19801 |
IR factor default ATM setpoint 2 |
|
19802 |
IR factor default ATM setpoint 3 |
|
19803 |
IR factor default ATM setpoint 4 |
|
19804 |
IR factor default TC setpoint 1 |
|
19805 |
IR factor default TC setpoint 2 |
|
19806 |
IR factor default TC setpoint 3 |
|
19807 |
IR factor default TC setpoint 4 |
|
19808 |
IR factor default factor 11 |
|
19809 |
IR factor default factor 12 |
|
19810 |
IR factor default factor 13 |
|
19811 |
IR factor default factor 14 |
|
19812 |
IR factor default factor 21 |
|
19813 |
IR factor default factor 22 |
|
19814 |
IR factor default factor 23 |
|
19815 |
IR factor default factor 24 |
|
19816 |
IR factor default factor 31 |
|
19817 |
IR factor default factor 32 |
|
19818 |
IR factor default factor 33 |
|
19819 |
IR factor default factor 34 |
|
19820 |
IR factor default factor 41 |
|
19821 |
IR factor default factor 42 |
|
19822 |
IR factor default factor 43 |
|
19823 |
IR factor default factor 44 |
|
19850 |
IR factor external ATM setpoint 1 |
|
19851 |
IR factor external ATM setpoint 2 |
|
19852 |
IR factor external ATM setpoint 3 |
|
19853 |
IR factor external ATM setpoint 4 |
|
19854 |
IR factor external TC setpoint 1 |
|
19855 |
IR factor external TC setpoint 2 |
|
19856 |
IR factor external TC setpoint 3 |
|
19857 |
IR factor external TC setpoint 4 |
|
19858 |
IR factor external factor 11 |
|
19859 |
IR factor external factor 12 |
|
19860 |
IR factor external factor 13 |
|
19861 |
IR factor external factor 14 |
|
19862 |
IR factor external factor 21 |
|
19863 |
IR factor external factor 22 |
|
19864 |
IR factor external factor 23 |
|
19865 |
IR factor external factor 24 |
|
19866 |
IR factor external factor 31 |
|
19867 |
IR factor external factor 32 |
|
19868 |
IR factor external factor 33 |
|
19869 |
IR factor external factor 34 |
|
19870 |
IR factor external factor 41 |
|
19871 |
IR factor external factor 42 |
|
19872 |
IR factor external factor 43 |
|
19873 |
IR factor external factor 44 |