Burnoff Setup
This menu option allows the user to modify the settings that are associated with the probe burnoff (menu option Burnoff).
Burnoff Time (sec)
The amount of time from the beginning of the burnoff to the end of the burnoff measured in seconds. The range is 0 to 600.
Burnoff Recovery Wait Time (sec)
The amount of time allotted to allow the probe measurements to return to a stable, accurate range after the burnoff is complete. This is measured in seconds. The control output is held until this time is elapsed. The range is 0 to 300.
Burnoff Interval (min)
The amount of time between the beginning of one burnoff and the beginning of the next scheduled burnoff measured in minutes. The range is 0 to 10080.
Burnoff Minimum Millivolts
The minimum measured millivolt tolerance of the probe required to start a burnoff. If the millivolts value is exceeded the burnoff will stop. This is done to help maintain the life and the accuracy of your probe. The range is 0 to 2000.
Burnoff Maximum Temperature
The maximum measured temperature allowed during a burnoff. If the temperature value is exceeded the burnoff will stop. This is done to help maintain the life and the accuracy of your probe. The range is 0 to 4000.