Appendix 1: Factory Default Values for HP15-VR
|
|
OXYGEN |
CARBON |
DEW POINT |
MILLIVOLTS |
|
Loop 1 Set Point: |
0.0 |
0.00 |
0 |
0 |
|
Temperature Set Point: |
0 |
0 |
0 |
0 |
|
Remote Set Point Setup: |
None |
None |
None |
None |
|
Hysteresis: |
0 |
0 |
0 |
0 |
|
Set Point: |
0 |
0.0% |
0 |
0 |
Temperature Mode
|
Temperature Mode: |
Fahrenheit |
Fahrenheit |
Fahrenheit |
Fahrenheit |
CO Factor
|
CO Factor: |
N/A |
200 |
N/A |
N/A |
H2 Factor
|
H2 Factor: |
N/A |
N/A |
400 |
N/A |
Pump Control
|
Current State: |
Off |
Off |
Off |
Off |
|
Low Temp. Pump Cutoff: |
Off |
Off |
Off |
Off |
Auto / Manual
|
Loop 1 Output: |
Automatic |
Automatic |
Automatic |
Automatic |
|
Loop 2 Output: |
Automatic |
Automatic |
Automatic |
Automatic |
|
PVT Type: |
Oxygen |
Carbon |
Dew Point |
Millivolts |
|
IP Address: |
192.168.0.200 |
192.168.0.200 |
192.168.0.200 |
192.168.0.200 |
|
Netmask: |
255.255.255.0 |
255.255.255.0 |
255.255.255.0 |
255.255.255.0 |
|
Gateway: |
192.168.1.1 |
192.168.1.1 |
192.168.1.1 |
192.168.1.1 |
Loop 1 PID Settings:
|
Proportional Band: |
20.0 |
20.0 |
20.0 |
20.0 |
|
Reset: |
0.10 |
0.10 |
0.10 |
0.10 |
|
Rate: |
0.00 |
0.00 |
0.00 |
0.00 |
|
Cycle Time: |
16 |
16 |
16 |
16 |
|
Integral Preset: |
0 |
0 |
0 |
0 |
|
Control Low Limit: |
0 |
-100 |
-100 |
-100 |
|
Control High Limit: |
100 |
100 |
100 |
100 |
|
Loop Mode: |
Single Reverse |
Dual Reverse |
Dual Direct |
Dual Reverse |
|
Auto PID: |
No |
No |
No |
No |
|
Switch Pt. PID 1 -> 2 |
999.9 |
99.99 |
9999 |
9999 |
|
Switch Pt. PID 2 -> 3 |
999.9 |
99.99 |
9999 |
9999 |
|
SP Lower Limit |
-999.9 |
-99.99 |
-9999 |
-9999 |
|
SP Upper Limit |
2999.9 |
299.99 |
29999 |
29999 |
Hi Limit Shuts Down Control:
|
|
Input 1: |
No |
No |
No |
No |
|
Input 2: |
No |
No |
No |
No |
|
|
Input 3: |
No |
No |
No |
No |
|
|
Zero Set Point Shuts Down Control: |
No |
Yes |
No |
Yes |
|
|
Set Point Change Limit: |
Off |
Off |
Off |
Off |
|
Config Menu (Continued)
|
|
OXYGEN |
CARBON |
DEW POINT |
MILLIVOLTS |
|
Proportional Band: |
4.4 |
4.4 |
4.4 |
4.4 |
|
Reset: |
0.12 |
0.12 |
0.12 |
0.12 |
|
Rate: |
2.16 |
2.16 |
2.16 |
2.16 |
|
Cycle Time: |
16 |
16 |
16 |
16 |
|
Integral Preset: |
0 |
0 |
0 |
0 |
|
Control Low Limit: |
0 |
0 |
0 |
0 |
|
Control High Limit: |
100 |
100 |
100 |
100 |
|
Loop Mode: |
Single Reverse |
Single Reverse |
Single Reverse |
Single Reverse |
|
Auto PID: |
No |
No |
No |
No |
|
Switch Pt. PID 1 -> 2 |
9999 |
9999 |
9999 |
9999 |
|
Switch Pt. PID 2 -> 3 |
9999 |
9999 |
9999 |
9999 |
|
SP Lower Limit |
-9999 |
-9999 |
-9999 |
-9999 |
|
SP Upper Limit |
29999 |
29999 |
29999 |
29999 |
|
|
Input 1: |
No |
No |
No |
No |
|
Input 2: |
Yes |
Yes |
Yes |
Yes |
|
|
Input 3: |
No |
No |
No |
No |
|
|
Zero Set Point Shuts Down Control: |
No |
No |
No |
No |
|
|
Set Point Change Limit: |
Off |
Off |
Off |
Off |
|
|
Burnoff Time (sec): |
90 |
90 |
90 |
90 |
|
Recovery Wait Time (sec): |
120 |
120 |
120 |
120 |
|
Interval: |
720 |
720 |
720 |
720 |
|
Minimum mV: |
800 |
800 |
800 |
800 |
|
Maximum Temperature: |
2000 |
2000 |
2000 |
2000 |
Analog Input Setup:
|
Input Type: |
2.5 Volts |
2.5 Volts |
2.5 Volts |
2.5 Volts |
|
Filter: |
2 |
2 |
2 |
2 |
|
Initial Scale: |
0 |
0 |
0 |
0 |
|
Full Scale: |
2500 |
2500 |
2500 |
2500 |
|
Decimal Point Location: |
0 |
0 |
0 |
0 |
|
Open Input Detection: |
One Trip Point |
Up Scale |
Up Scale |
Up Scale |
|
Trip 1 Direction: |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
|
Trip 2 Direction: |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
|
Offset: |
0 |
0 |
0 |
0 |
|
Trip Point 1 Set Point: |
1400 |
0 |
0 |
0 |
|
Trip Point 1 Force Value: |
0 |
0 |
0 |
0 |
|
Trip Point 2 Set Point: |
0 |
0 |
0 |
0 |
|
Trip Point 2 Force Value: |
0 |
0 |
0 |
0 |
|
Hi Input Limit SP |
0 |
9999 |
9999 |
9999 |
|
Hi Input Limit Hysteresis |
0 |
1 |
1 |
1 |
Analog Input 2 Settings:
|
Input Type: |
Type B |
Type S |
Type S |
Type S |
||||
|
Filter: |
2 |
2 |
2 |
2 |
||||
|
Initial Scale: |
0 |
0 |
0 |
0 |
||||
|
Full Scale: |
10000 |
10000 |
10000 |
10000 |
||||
|
Decimal Point Location: |
0 |
0 |
0 |
0 |
||||
|
Open Input Detection: |
Down Scale |
Up Scale |
Up Scale |
Up Scale |
||||
|
Trip 1 Direction: |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
||||
|
Trip 2 Direction: |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
Input Above Set Point |
||||
|
Offset: |
0 |
0 |
0 |
0 |
||||
|
Trip Point 1 Set Point: |
0 |
0 |
0 |
0 |
||||
|
Trip Point 1 Force Value: |
0 |
0 |
0 |
0 |
||||
|
Trip Point 2 Set Point: |
|
|||||||
|
||||||||
0 |
1800 |
1800 |
1800 |
|||||
|
Hi Input Limit Hysteresis |
0 |
1 |
1 |
1 |
Config Menu (Continued)
|
|
OXYGEN |
CARBON |
DEW POINT |
MILLIVOLTS |
|
Input Type: |
Type S |
Type S |
Type S |
Type S |
|
Filter: |
2 |
2 |
2 |
2 |
|
Initial Scale: |
0 |
0 |
0 |
0 |
|
Full Scale: |
10000 |
10000 |
10000 |
10000 |
|
Decimal Point Location: |
0 |
0 |
0 |
0 |
|
Open Input Detection: |
Up Scale |
Up Scale |
Up Scale |
Up Scale |
|
Trip 1 Direction: |
Above Set Point |
Above Set Point |
Above Set Point |
Above Set Point |
|
Trip 1 Direction: |
Above Set Point |
Above Set Point |
Above Set Point |
Above Set Point |
|
Offset: |
0 |
0 |
0 |
0 |
|
Trip Point 1 Set Point: |
0 |
0 |
0 |
0 |
|
Trip Point 1 Force Value: |
0 |
0 |
0 |
0 |
|
Trip Point 2 Set Point: |
0 |
0 |
0 |
0 |
|
Trip Point 2 Force Value: |
0 |
0 |
0 |
0 |
|
Hi Input Limit SP |
0 |
9999 |
9999 |
9999 |
|
Hi Input Limit Hysteresis |
0 |
1 |
1 |
1 |
Analog Output Setup:
|
Analog Output 1 Assignment: |
PV1 Retrans |
PV1 Retrans |
PV1 Retrans |
PV1 Retrans |
|
Exponent: |
0 |
0 |
0 |
0 |
|
Full Scale: |
2000 |
2000 |
2000 |
2000 |
|
Range |
209 |
200 |
200 |
200 |
|
Offset: |
0 |
0 |
0 |
0 |
|
O2 Exponent Range |
0 |
0 |
0 |
0 |
|
Current Selection |
4-20mA |
4-20mA |
4-20mA |
4-20mA |
|
Analog Output 2 Assignment: |
Loop 2 Inc. |
Loop 2 Inc. |
Loop 2 Inc. |
Loop 2 Inc. |
|
Exponent: |
0 |
0 |
0 |
0 |
|
Full Scale: |
2000 |
2000 |
2000 |
2000 |
|
Range |
3000 |
2000 |
2000 |
2000 |
|
Offset: |
0 |
0 |
0 |
0 |
|
O2 Exponent Range |
0 |
0 |
0 |
0 |
|
Current Selection |
4-20mA |
4-20mA |
4-20mA |
4-20mA |
Alarms:
|
Alarm Source: |
Input 2 |
Input 2 |
Input 2 |
Input 2 |
|
|
Alarm Action: |
Process High |
Process High |
Process High |
Process High |
|
|
Alarm Set Point: |
1800 |
1800 |
1800 |
1800 |
|
|
Smart Alarm: |
Disabled |
Disabled |
Disabled |
Disabled |
|
|
0 SP Blocks Alarm: |
No |
No |
No |
No |
|
|
Hysteresis: |
1 |
1 |
1 |
1 |
|
|
On Delay Time: |
0 |
0 |
0 |
0 |
|
|
|
Alarm Source: |
Input 2 |
Input 2 |
Input 2 |
Input 2 |
|
Alarm Action: |
Process High |
Process High |
Process High |
Process High |
|
Alarm Set Point: |
2000 |
2000 |
2000 |
2000 |
|
Smart Alarm: |
Disabled |
Disabled |
Disabled |
Disabled |
|
0 SP Blocks Alarm: |
No |
No |
No |
No |
|
Hysteresis: |
1 |
1 |
1 |
1 |
|
On Delay Time: |
0 |
0 |
0 |
0 |
|
Polarity |
Normally Open |
Normally Open |
Normally Open |
Normally Open |
Alarm 3 Settings:
|
Alarm Source: |
PV1 |
PV2 |
PV2 |
PV2 |
|
Alarm Action: |
Process Low |
Process High |
Process High |
Process High |
|
Alarm Set Point: |
1.0 |
2000 |
2000 |
2000 |
|
Smart Alarm: |
Disabled |
Disabled |
Disabled |
Disabled |
|
0 SP Blocks Alarm: |
No |
No |
No |
No |
|
Hysteresis: |
1 |
1 |
1 |
1 |
|
On Delay Time: |
0 |
0 |
0 |
0 |
|
Polarity |
Normally Open |
Normally Open |
Normally Open |
Normally Open |