Universal Defaults

  • Temperature in °F

  • All Baud Rates initially 19200 and set for Modbus

  • Burnoff time is 90 seconds

  • Burnoff recovery wait time is 2 minutes

  • Burnoff interval is 12 hours

  • Burnoff maximum temperature is 2000 °F

  • CO Factor is 200

  • Hydrogen factor for Dewpoint calculation is 40%

  • Analog to Digital Converter filter time is 8 seconds for all 3 ADCs

  • For analog input 1 initial scale is 0, and full scale is 1000

  • For analog input 2 initial scale is 0, and full scale is 10000

  • For analog input 3 initial scale is 0, and full scale is 10000

  • First Process Control Setpoint is set to 0

  • First Process Proportional Band is 20%

  • First Process Reset for PID control is On

  • First Process Rate for PID control is 0

  • First Process Output Cycle Time for Control is 16 milliseconds

  • First Process Auto/Manual set to Automatic

  • First Process Control Load Line or Manual Reset (integral preset) set to 0

  • Second Process Control Setpoint is set to 0

  • Second Process Proportional Band is 4.4%

  • Second Process Reset for PID control is 12

  • Second Process Rate for PID control is 216

  • Second Process Output Cycle Time for Control is 60 milliseconds

  • Second Process Auto/Manual set to Automatic

  • Second Process Control Load Line or Manual Reset (integral preset) set to 0

  • Start PV for temporary tuning set to 0

  • Temporary Proportional band for tuning set to 2%

  • Temporary reset for tuning set to On

  • Temporary rate for tuning set to 0

  • Temporary integral preset for tuning set to 0

  • Relay 1 set for loop 2 heat

  • Relay 2 set for alarm 1

  • Relay 3 set for loop 1 increment (gas)

  • Relay 4 set for loop 1 decrement (air)

  • Relay 5 fixed by PV type.

  • Relay 6 set for Probe Burnoff

  • Relay 7 set for Alarm 3

  • Relay 8 set for all alarms.

  • Alarm 1 setpoint set for 1800

  • Alarm 1 is set for analog input 2

  • Alarm 1 hysteresis is set for 1

  • Alarm 2 setpoint set for 2000

  • Alarm 2 is set for analog input 1

  • Alarm 2 hysteresis is set for 1

  • Alarm 3 setpoint set for 2000

  • Alarm 3 is set for process variable 2

  • Alarm 3 hysteresis is set for 1

  • Digital to Analog converter 1 assignment is PV1 retransmit

  • Digital to Analog converter 2 assignment is loop 2 increment

  • Default IP is 192.168.0.200