Universal Defaults
-
Temperature in °F
-
All Baud Rates initially 19200 and set for Modbus
-
Burnoff time is 90 seconds
-
Burnoff recovery wait time is 2 minutes
-
Burnoff interval is 12 hours
-
Burnoff maximum temperature is 2000 °F
-
CO Factor is 200
-
Hydrogen factor for Dewpoint calculation is 40%
-
Analog to Digital Converter filter time is 8 seconds for all 3 ADCs
-
For analog input 1 initial scale is 0, and full scale is 1000
-
For analog input 2 initial scale is 0, and full scale is 10000
-
For analog input 3 initial scale is 0, and full scale is 10000
-
First Process Control Setpoint is set to 0
-
First Process Proportional Band is 20%
-
First Process Reset for PID control is On
-
First Process Rate for PID control is 0
-
First Process Output Cycle Time for Control is 16 milliseconds
-
First Process Auto/Manual set to Automatic
-
First Process Control Load Line or Manual Reset (integral preset) set to 0
-
Second Process Control Setpoint is set to 0
-
Second Process Proportional Band is 4.4%
-
Second Process Reset for PID control is 12
-
Second Process Rate for PID control is 216
-
Second Process Output Cycle Time for Control is 60 milliseconds
-
Second Process Auto/Manual set to Automatic
-
Second Process Control Load Line or Manual Reset (integral preset) set to 0
-
Start PV for temporary tuning set to 0
-
Temporary Proportional band for tuning set to 2%
-
Temporary reset for tuning set to On
-
Temporary rate for tuning set to 0
-
Temporary integral preset for tuning set to 0
-
Relay 1 set for loop 2 heat
-
Relay 2 set for alarm 1
-
Relay 3 set for loop 1 increment (gas)
-
Relay 4 set for loop 1 decrement (air)
-
Relay 5 fixed by PV type.
-
Relay 6 set for Probe Burnoff
-
Relay 7 set for Alarm 3
-
Relay 8 set for all alarms.
-
Alarm 1 setpoint set for 1800
-
Alarm 1 is set for analog input 2
-
Alarm 1 hysteresis is set for 1
-
Alarm 2 setpoint set for 2000
-
Alarm 2 is set for analog input 1
-
Alarm 2 hysteresis is set for 1
-
Alarm 3 setpoint set for 2000
-
Alarm 3 is set for process variable 2
-
Alarm 3 hysteresis is set for 1
-
Digital to Analog converter 1 assignment is PV1 retransmit
-
Digital to Analog converter 2 assignment is loop 2 increment
-
Default IP is 192.168.0.200