INSTRUMENT SETUP –
The instrument should be fully configured at the factory for immediate use. In the event that the settings are ever lost, the following charts show the appropriate configuration and operative (runtime) parameters for the Series 8 controller. How to navigate the Series 8 controller can be found in the 800 Range Quick Start Guide, which was included with the DPC2530. Additional information on the Series 8 controller can also be found on the SSi website.
If using a 7EK controller, please see Appendix E: 7EK Information
When the instrument is set up in Fahrenheit using these parameters, the input is scaled from –50 to +80°F and the 4-20mA output is scaled from –50 to +80°F. When the instrument is set up in
Celsius using these parameters, the input is scaled from –45.6 to +26.7°C and the 4-20mA output is scaled from –45 to +25°C.
Series 8 Configuration Parameters |
||
---|---|---|
Parameter |
Fahrenheit |
Celsius |
P1 |
MV |
MV |
P2 |
NNNN |
NNNN |
P3 |
-50 |
-45.6 |
P4 |
80 |
26.7 |
P5 |
0 |
0 |
P6 |
80 |
80 |
P7 |
NONE |
NONE |
P11 |
NONE |
NONE |
P12 |
NONE |
NONE |
P13 |
PV.RT |
PV.RT |
P14 |
NONE |
NONE |
P15 |
4.20 |
4.20 |
P21 |
NONE |
NONE |
P24 |
NONE |
NONE |
P27 |
NONE |
NONE |
P31 |
NONE |
NONE |
P32 |
100 |
100 |
P33 |
NONE |
NONE |
P34 |
OFF |
OFF |
P35 |
ON |
ON |
P36 |
0 |
0 |
P37 |
NONE |
NONE |
P41 |
NONE |
NONE |
P51 |
T.RRS |
T.RRS |
P52 |
T.HLD |
T.HLD |
P61 |
1 |
1 |
P62 |
19.20 |
19.20 |
P63 |
NONE |
NONE |
P64 |
NONE |
NONE |
P71 |
A-M |
A-M |
P72 |
T.ST |
T.ST |
P73 |
AC.AL |
AC.AL |
P74 |
STD |
STD |
P75 |
OP |
OP |
P76 |
2 |
2 |
P77 |
4 |
4 |
P81 |
NONE |
NONE |
rEcS |
NONE |
NONE |
rEcL |
NONE |
NONE |
PHAS |
NONE |
NONE |
Series 8 Operative (runtime) Parameters |
||
---|---|---|
Parameter |
Fahrenheit |
Celsius |
OP |
0 |
0 |
Unit |
°F |
°C |
SPLo |
0 |
0 |
SPHI |
80 |
26.7 |
SP1 |
0 |
0 |
SP2 |
0 |
0 |
SP.SL |
SP1 |
SP1 |
SPrr |
OFF |
OFF |
oFS |
0 |
0 |
FILt |
1.6 |
1.6 |
oPLo |
0 |
0 |
oPHI |
0 |
0 |
LdAL |
OFF |
OFF |
LEAL |
OFF |
OFF |
Ld.AL |
OFF |
OFF |
HcAL |
OFF |
OFF |
UcAL |
IDLE |
IDLE |
In addition to these parameters, a voltage divider must be installed to the dew point input (This divider is installed at the factory prior to shipment.)