Analog Output Setup
The 9220 controller has two analog outputs. The outputs can be configured for 0 – 20 milliamp signal or a 4 – 20 milliamp signal. Each output comes with a factory default configuration dependent on the application. Each output can be modified prior to shipment to your facility or in the field by a supervisor.
Analog Output Terminals:
Analog output 1 – terminals 24(-) and 25(+)
Analog output 2 – terminals 25(+) and 26(-)
Assignment:
The analog output assignment can be modified depending on your system requirements. To change the Assignment first select which analog output you want to change by selecting it in the pull-down menu just below the main menu list. Clicking on this value will display an input box, and then you can use the pull-down menu to select the desired parameter. Once selected click OK and the displayed assignment under Value will be the current assignment type. The following is a list of the options:
PV 1 retrans
Loop 1 inc
Loop 1 dec
Loop 1 combo
PV 2 retrans
Loop 2 inc
Loop 2 dec
Loop 2 combo
PV3 retrans
Loop 3 inc
Loop 3 dec
Loop 3 combo
Input 1 retrans
Input 2 retrans
Input 3 retrans
SP1 retrans
SP2 retrans
SP3 retrans
Programmer ID num
PV switch loop inc
PV switch loop dec
PV switch loop combo
Gauge 1 log of torr
Gauge 1 linear torr
Gauge 1 microns
Gauge 2 linear torr
Gauge 2 log of torr
Gauge 2 microns
Gauge 3 linear torr
Gauge 3 log of torr
Gauge 3 microns
Gauge 4 linear torr
Gauge 4 log of torr
Gauge 4 microns
Programmer Analog Out 1
Programmer Analog Out 2
Programmer Analog Out 3
Programmer Analog Out 4
Programmer Analog Out 5
Programmer Analog Out 6
Disabled
NOTE: The ‘Disabled’ setting allows the external device to write directly to the output register of the 9220’s internal Digital Analog Converter.
Combo example for carbon – 4 – 12 mA Air
12 – 20 mA Gas
Offset:
This is the starting point, the Process Variable value at which you get 4 milliamps. Normally, when scaling a control output, this would be the low range and is set up for 0. This value can vary depending on the scaling needs. Clicking on this value will display an input box from which the user can select a new value. The range is –32768 to 32767.
Range:
This is a Process Variable value between 4 and 20 milliamps. Normally, when scaling a control output, this would be the low range and is set up for 100. This value can vary depending on the scaling needs. Clicking on this value will display an input box from which the user can select a new value. The range is –32768 to 32767.
Current Selection:
Provides the option of 4-20 mA or 0-20 mA control. Clicking on this value will display an input box with a drop-down list from which the user can select either of the two values listed above.
Offset and Range when assigned to a control loop:
Inc -- 0 = 4mA, 100 = 20mA
Dec -- 0 = 4mA, -100 = 20mA
Example: if 4 – 20 mA = 800 mV - 1200 mV
Offset = 800 (starting point)
Range = 400