Flow Set Point Configuration
This menu provides options for setting flow rate minimum and preset values.
Carburize Minimum Endo Flow When in %Carbon mode (not Nitriding or FNC), this sets the minimum endothermic gas rate into the furnace. Either or both valve 3 and 4 must be set to endo valve type in order for this feature to work. If the endothermic gas target setpoint for valve 3 or 4 is less than this minimum, then the setpoint is set to the minimum. The controller will check both valves 3 and 4 and adjust the setpoints independently, if needed. If the value for this option is set to 0, then the feature is disabled (not used). |
|
Valve presets (applies to Carburize preset – N2, NH3, D.A., and H2 valves, and FNC preset – N2, NH3, D.A., and H2 valves)
In total, there are eight (8) presets for valve setpoints used when switching between %C and FNC modes. Valves 1 is assumed to be for N2, valve 2 for NH3, valve 3 for D.A., and valve 4 for H2.
Two basic principles are important for these options:
-
When switching from FNC mode to %C mode, the Carburize presets are used.
-
When switching from %C mode to FNC mode, the FNC presets are used.
The preset for each valve can have one of three conditions:
-
The preset can be disabled, meaning the valve setpoint will not be changed.
-
The preset can be set to current flow, which means that the setpoint will be set to the actual flow through the valve when the switch occurs.
-
The preset can be set to a specific value, which will be applied to the specified valve when the mode switch occurs.
The presets are used only when the switch occurs from %C to FNC, or from FNC to %C. No changes to the valve setpoints will occur once the mode switch has taken place (unless the mode switches again).