Atmosphere Instruments

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

AC20

11

123

1

1

%C Actual

(Modbus Mode)

29

138

1

1

%C Setpoint

 

13

125

1

1

Probe Temperature

 

10

122

1

1

Probe Millivolts

 

20

130

10

10

%C Percent Output

 

34

142

1

1

CO Factor or Equivalent

 

35

143

1

1

H Factor or Equivalent

 

12

124

1

1

Dew Point

 

36

144

10

10

O2

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Yoko 750

2

2

1

1

%C Actual

(Modbus Mode)

3

100

1

1

%C Setpoint

 

20

19

1

1

Probe Temperature

 

10

122

1

1

Probe Millivolts

 

4

4

10

10

%C Percent Output

 

0

0

1

1

CO Factor or Equivalent

 

0

0

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

UDC 3300’s

1

0

1

1

%C Actual

(Modbus Mode)

3

2

1

1

%C Setpoint

 

6

5

10

10

Probe Temperature

 

5

4

10

10

Probe Millivolts

 

4

3

10

10

%C Percent Output

 

43

39

10

10

CO Factor or Equivalent

 

43

39

10

10

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Dualpro Loop 1

21

20

1

1

%C Actual

(Modbus Mode)

7

6

1

1

%C Setpoint

 

18

17

8

8

Probe Temperature

 

19

18

8

8

Probe Millivolts

 

41

40

41

41

%C Percent Output

 

4

3

1

1

CO Factor or Equivalent

 

5

4

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Dualpro Loop 2

21

20

1

1

%C Actual

(Modbus Mode)

8

7

1

1

%C Setpoint

 

18

17

8

8

Probe Temperature

 

19

18

8

8

Probe Millivolts

 

42

41

41

41

%C Percent Output

 

4

3

1

1

CO Factor or Equivalent

 

5

4

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Dualpro Loop 1

20

20

1

1

%C Actual

(MMI Mode)

6

6

1

1

%C Setpoint

 

17

17

8

8

Probe Temperature

 

18

18

8

8

Probe Millivolts

 

40

40

41

41

%C Percent Output

 

3

3

1

1

CO Factor or Equivalent

 

4

4

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Dualpro Loop 2

20

20

1

1

%C Actual

(MMI Mode)

7

7

1

1

%C Setpoint

 

17

17

8

8

Probe Temperature

 

18

18

8

8

Probe Millivolts

 

41

41

41

41

%C Percent Output

 

3

3

1

1

CO Factor or Equivalent

 

4

4

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Eurotherm 2404

1

1

1

1

%C Actual

(Modbus Mode)

5

5

1

1

%C Setpoint

 

72

11073

1

1

Probe Temperature

 

61

11062

1

1

Probe Millivolts

 

4

4

1

1

%C Percent Output

 

0

0

1

1

CO Factor or Equivalent

 

0

0

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Eurotherm 2500

1

1

1

1

%C Actual

(Modbus Mode)

5

5

1

1

%C Setpoint

 

72

11073

1

1

Probe Temperature

Assumes Loop 1 =

61

11062

1

1

Probe Millivolts

Atmosphere

4

4

1

1

%C Percent Output

 

68

11069

1

1

CO Factor or Equivalent

 

68

11069

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Carbpro 3.5

6

28

1

1

%C Actual

(MMI Mode)

1

1

1

1

%C Setpoint

 

5

25

8

8

Probe Temperature

 

4

24

8

8

Probe Millivolts

 

11

117

1

1

%C Percent Output

 

13

7

1

1

CO Factor or Equivalent

 

14

8

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Carbpro 3.0

6

28

4

4

%C Actual

(MMI Mode)

1

1

1

1

%C Setpoint

 

5

25

8

8

Probe Temperature

 

4

24

2

2

Probe Millivolts

 

11

117

1

1

%C Percent Output

 

13

7

1

1

CO Factor or Equivalent

 

14

8

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Carbpc

20

20

1

1

%C Actual

(MMI Mode)

6

6

1

1

%C Setpoint

 

17

17

8

8

Probe Temperature

 

18

18

8

8

Probe Millivolts

 

64

64

41

41

%C Percent Output

 

3

3

1

1

CO Factor or Equivalent

 

4

4

1

1

H Factor or Equivalent

 

Controller

Source Location

Write Register

Read Scale

Write Scale

Description

Series 9200 Loop 1

3

126

1

1

%C Actual

 

5

128

1

1

%C Setpoint

 

22

145

1

1

Probe Temperature

 

21

144

10

10

Probe Millivolts

 

7

130

10

10

%C Percent Output

 

19

142

1

1

CO Factor or Equivalent

 

20

143

1

1

H Factor or Equivalent