DF1 Configuration

 

This option allows the information data from the 9215 to be sent to the PLC DF1 Register map.

 

My node

This option will allow the user to select the node.  This node must not exist anywhere else on the computer’s network.  The range is 0 to 30000.

 

PLC node

This option will allow the user to select the PLC node.  This must be the node address of a PLC.  The range is 0 to 30000.

 

PLC  read table

This option will allow the user to select the PLC read table.  The range is 8 to 255.

 

PLC  write table

This option will allow the user to select the PLC write table.  The range is 8 to 255.

 

PLC intermessage delay

This is the delay time (in milliseconds) between requests sent to the PLC from the 9215 controller. The request can be for any read or write transaction between the PLC and the 9215. The range is 51 to 5000.