This option will allow the user to set up the valves for the 9210 Nitrider. There is a choice of four valves.
Zero Scale
The Zero Scale option will allow the user to set the zero scale for the valve. This value must be less than or equal to the Valve Max value.
Full Scale
This option will allow the user to set the full scale for the vale. This value must be less than or equal to the Valve Max value.
Trim Enable
This option will allow the user to set the trim enable option for the valve. The options are Yes or No.
Target Setpoint
The Target Setpoint option will allow the user to set the target setpoint for the valve. This value must be less than or equal to the Valve Max value.
Trim Range
This option will allow the user to set the trim range for the valve. This value must be less than or equal to the Valve Max value.
Zero SP Scale
This option will allow the user to set the zero scale for the setpoint. This value must be less than or equal to the Valve Max value.
Full SP Scale
This option will allow the user to set the full scale for the setpoint. This value must be less than or equal to the Valve Max value.
Valve Max
This option will allow the user to set the maximum flow rate for the valve. The range is 0 to 32767.
Deviation Setpoint
This option will allow the user to set the deviation setpoint for the valve. The range is 0 (OFF) to 32000.
Deviation Alarm Delay (Seconds)
This option will allow the user to set the deviation alarm delay, listed in 1/10th of minutes. The range is 0 to 32000. Note: The alarm delay is entered in 1/10th of a minute intervals, but it is displayed in seconds, so 3/10 of a minute = 18 seconds.
Gas Type
This option will determine the gas type for the valve.
Valve Decimal Place
This option will set the decimal place for the valve. The range is 0 through 4.
Standard Setup for Flow Alarms with Delays
The “Deviation Setpoint” is the flow alarm setpoint, and the “Dev. Alarm Delay (sec)” is the flow alarm delay time
|
Valve 1 |
Valve 2 |
Valve 3 |
Valve 4 |
Zero Scale |
0 |
0 |
0 |
0 |
Full Scale |
300 |
300 |
150 |
0 |
Trim Enable |
No |
Yes |
No |
no |
Target Setpoint |
150 |
150 |
10 |
0 |
Trim Range |
0 |
50 |
25 |
0 |
Zero SP Scale |
0 |
0 |
0 |
0 |
Full SP Scale |
300 |
300 |
150 |
0 |
Valve Max |
300 |
300 |
150 |
0 |
Deviation Setpoint |
20 |
60 |
10 |
Off |
Dev. Alarm Delay (sec) |
300 |
60 |
300 |
0 |
Gas Type |
Nitrogen |
Ammonia |
Dissociated Ammonia |
Hydrogen |
Valve Decimal Place |
0 |
0 |
0 |
0 |