Controller Description


The Model 9210-Nitriding instrument is a multi-loop Proportional Integral Derivative (PID) controller that can be custom configured to control up to three Nitriding process loops.  General features of this product include:

 

The Model 9210 is powered by 24 VDC, NOT LINE Voltage. Please be careful when connecting power to this controller. Connecting anything other then 24 VDC will cause serious damage.

 

 

Approximate Box Dimensions

2.75" x 4" x 4.5"

Power Requirements

24VDC, 4 Watts

Temperature Range

32˚F - 132˚F

Digital Output Rating

300VAC / 1 AMP

Analog Output Load Rating

1000 Ohms (Total)

Controller Enclosure Rating

IP10 – hand protected

Number of RS232 Ports

Two (2)

Number of Ethernet Ports

One (1)

Number of RS485 Host Ports

One (1)

Number of RS485 client Ports

Two (2)

Number of Internal Relays

Eight (8)

Number of Analog Inputs

Three (3)

Number of Analog Outputs

Two (2)

Number of Digital Inputs

Four (4)

Number of Control Loops

Three (3)

 

 

 

The control enclosure is powered by 120 VAC, Single Phase, 60 Hz (Line Power). Line voltage for the isolation relays comes from the same source.