Analog Input Setup
This menu option displays a two-level screen with the top level showing the three inputs. Use the blue up and down arrow keys to select one of the inputs.
Pressing the “Enter” key takes you to a menu of parameters that can be assigned to any of the three inputs. Included are thermocouples, voltage, and current inputs.
The lower zone of the “Analog Input Setup” screen contains a table:
Parameter |
Value |
TC Type |
S |
Filter Time |
0 |
Initial Scale |
0 |
Full Scale |
3000 |
Decimal Point Location |
0 |
Open TC |
Up scale |
Input offset |
0 |
Use curve |
0 |
Select the “TC Type” option and press the Enter button. This will display a screen with the different input types available. Note: See the Input type selections for the Series 9210 below for the different input types available. The “Filter Time” selection will display a numeric keypad from which the user can enter the new filter time. This can range from 0 to 9999. The “Initial Scale” selection will display a numeric keypad from which the user can enter the new initial scale. This can range from -9999 to 9999. The “Full Scale” selection will display a numeric keypad from which the user can enter the new full scale. This can range from –999- to 9999. The “Decimal Point Location” selection will display a numeric keypad from which the user can enter the new decimal point location. This can range from 0 to 4. The “Open TC” selection will display a screen from which the user can enter the new filter time. This can be either Up Scale or Down Scale. The “Input Offset” selection will display a numeric keypad from which the user can enter the new input offset. This can range from -10 to 10. The “Use Curve” selection will display a numeric keypad from which the user can enter the new curve to use. This can range from 0 to 5. 0 means no curve is used.
Continue until all values associated/required by the input type have been entered. Pressing the Esc key takes you back to the configuration menu.
Input type selections for the Series 9210:
Input Type Options |
T/C’s B, C, E, J, K, N, NNM, R, S, T |
|
2.5 Volts |
|
1.25 Volts |
|
78.125 Millivolts |
|
19.53125 Millivolts |
|
4 – 20 mA (124 Ohm precision shunt required) |
|
25 Volts (Requires internal jumper) |
|
12.5 Volts (Requires internal jumper) |
|
781.25 Millivolts (Requires internal jumper) |
|
195.3125 Millivolts (Requires internal jumper) |