Alarm Setup
The Alarm Setup menu is a two-level screen. The first level allows you to select the alarm – Alarm1 – Alarm 3. The Second level scrolls through the alarm parameters.
Parameter |
Value |
Setpoint |
2500 |
Alarm Type |
PV2 proc high |
Hysteresis |
1 |
|
|
Using the lower blue up and down arrow keys, select the parameter to modify, and then press the Enter button. The “Setpoint” selection will allow the user to enter the setpoint for the alarm. This will display a numeric keypad. This can range from –9999 to 9999. The “Alarm Type” selection will allow the user to set the type of alarm. This will display a two-level screen. The top level has the following options:
Process High
Process Low
Band, Normally Open
Band, Normally Closed
Deviation, Normally Open
Deviation, Normally Closed
The bottom level has the following options:
PV 1 Value
PV 2 Value
PV 3 Value
Input 1 Value
Input 2 Value
Input 3 Value
PO1 Value
PO2 Value
PO3 Value
The “Hysteresis” selection will allow the user to set the hysteresis. This will display a numeric keypad. This can range from 0 to 9999.
If you are configuring more than one alarm, follow the above instructions for each alarm that you are configuring.
Standard Setup for DA Alarm with Delays
DA is usually set up as PV 1 (Loop 1)
8.00 = 8% D.A.
Parameter |
Value |
Setpoint |
8.00 |
Alarm Type |
PV1 Band NO (Out of Band) |
Hysteresis |
1 |
Smart Alarm |
Disabled |
ON Delay Time (sec) |
3600 |