Appendix 5 – 9210 Nitrider Typical Configuration

Revision

 

Revision

1.68

PID Loop 1 Setup

 

Prop Band (0 for On/Off)

35.0

Reset

0.50

Rate

0.00

Mode

Dual Direct

Integral Preset

0

Cycle Time

24

Setpoint Change Limit

Off

Low Limit

-100

High Limit

100

0 Setpoint stops control

No

IN1 high limit shuts down ctrl

No

IN2 high limit shuts down ctrl

No

IN3 high limit shuts down ctrl

No

PID auto switch

No

Switch point PID 1 " 2

99.99

Switch point PID 2 " 3

99.99

Overshoot limit gain

0

Deviation setpoint

Off

Dev. Alarm delay (sec)

0

Setpoint lower limit

-99.99

Setpoint upper limit

299.99

PID Loop 2 Setup

 

Prop Band (0 for On/Off)

5.0

Reset

0.04

Rate

0.00

Mode

Single Reverse

Integral Preset

0

Cycle Time

6

Setpoint Change Limit

40 %

Low Limit

0

High Limit

100

0 Setpoint stops control

No

IN1 high limit shuts down ctrl

No

IN2 high limit shuts down ctrl

No

IN3 high limit shuts down ctrl

No

PID auto switch

No

Switch point PID 1 " 2

9999

Switch point PID 2 " 3

9999

Overshoot limit gain

0

Setpoint lower limit

-9999

Setpoint upper limit

9999

PID Loop 3 Setup

 

Prop Band (0 for On/Off)

20.0

Reset

0.50

Rate

0.00

Mode

Single Reverse

Integral Preset

0

Cycle Time

60

Setpoint Change Limit

Off

Low Limit

0

High Limit

100

0 Setpoint stops control

No

IN1 high limit shuts down ctrl

No

IN2 high limit shuts down ctrl

No

IN3 high limit shuts down ctrl

No

PID auto switch

No

Switch point PID 1 " 2

99.99

Switch point PID 2 " 3

99.99

Overshoot limit gain

0

Deviation setpoint

Off

Dev. Alarm delay (sec)

0

Setpoint lower limit

-99.99

Setpoint upper limit

299.99

Event Run Program Setup

 

Program number to run

0

Load TC Setup

 

Load TC Enable

Off

Control TC

 

TC 1

 

TC 2

 

TC 3

 

TC 4

 

TC 5

 

TC 6

 

TC 7

 

TC 8

 

TC 9

 

TC 10

 

TC 11

 

TC 12

 

TC 13

 

TC 14

 

TC 15

 

TC 16

 

TC 17

 

TC 18

 

TC 19

 

TC 20

 

TC 21

 

TC 22

 

TC 23

 

TC 24

 

Port Setup

 

Host 232 Baud

19200

Host 232 Mode

Modbus Master/PLC

Host 485 (3,4) Baud

19200

Host 485 (3,4) Mode

Modbus

Host 485 Address

1

client 1 (5,6) Baud

19200

client 1 (5,6) Mode

Modbus Host

client 2 (22,23) Baud

19200

client 2 (22,23) Mode

Modbus

232/H2 Port Baud

9600

PLC Type

Micrologix Modbus

client Instrument Setup

 

Instrument 1

SSi 7SL @ 2 on client 2

Instrument 2

SSi 7SL @ 3 on client 2

Instrument 3

9100 LP2 @ 5 on client 2

Instrument 4

 

Instrument 5

 

Instrument 6

 

Instrument 7

 

Instrument 8

 

Instrument 9

 

Instrument 10

 

Instrument 11

 

Instrument 12

 

Instrument 13

 

Instrument 14

 

Instrument 15

 

Instrument 16

 

Instrument 17

 

Instrument 18

 

Instrument 19

 

Instrument 20

Micrologix PLC @ 1 on RS-232

Instrument 21

Micrologix PLC @ 1 on RS-232

Instrument 22

Micrologix PLC @ 1 on RS-232

Instrument 23

 

Instrument 24

 

Instrument 25

Micrologix PLC @ 1 on RS-232

Zone 1 Assignment

 

Atm Instrument

Loop 1

Atm Zone Number

0

Default Zone offset, atm

0.00

Temp instrument

Loop 1

Temp zone number

0

Default zone offset, temp

0

Zone 2 Assignment

 

Atm Instrument

Loop 1

Atm Zone Number

0

Default Zone offset, atm

0.00

Temp instrument

Loop 1

Temp zone number

0

Default zone offset, temp

0

Zone 3 Assignment

 

Atm Instrument

Loop 1

Atm Zone Number

0

Default Zone offset, atm

0.00

Temp instrument

Loop 1

Temp zone number

0

Default zone offset, temp

0

Zone 4 Assignment

 

Atm Instrument

Loop 1

Atm Zone Number

0

Default Zone offset, atm

0.00

Temp instrument

Loop 1

Temp zone number

0

Default zone offset, temp

0

Zone 5 Assignment

 

Atm Instrument

Loop 1

Atm Zone Number

0

Default Zone offset, atm

0.00

Temp instrument

Loop 1

Temp zone number

0

Default zone offset, temp

0

Furnace Setup

 

PVT Type

Nitrider

Nitrider Mode

H2 and Dissociation

Nitrider Control

Control

H2 cell type

Hi

H2 RS-232 Comms

Yes

Temperature Display

Internal

Lp3 control

Backpressure

Valve 1 (Nitrogen)

Yes

Valve 2 (Ammonia)

Yes

Dissociated Ammonia

Yes

Hydrogen

No

Temperature mode

F

Programmer type

Nitrider

Atmosphere instrument

Loop 1

Temperature instrument

Loop 2

Event instrument

Instrument 20

Quench instrument

Instrument 13

End of quench event

0

Quench speed event

0

Quench run event

0

Nitrider bias

0.0

Date and time

<System Date>

Default hold time (min)

5

Deviation alarm delay (min)

0

PLC type

Micrologix Modbus

Flow signal

Analog/PLC

Clear events, end of recipe

No

Wait Limits

 

Temp wait limit

25

Atm wait limit

1.0

Furnace Name

 

Furnace Name

Nitrider 83

PV1 Name

 

PV2 Name

 

PV3 Name

 

Alarm 1 Setup

 

Setpoint

800

Alarm Type

PV1 Band NO

Hysteresis

1

Smart Alarm

Disabled

ON Delay Time (sec)

3600

Alarm 2 Setup

 

Setpoint

1400

Alarm Type

PV2 proc high

Hysteresis

10

Smart Alarm

Disabled

ON Delay Time (sec)

0

Alarm 3 Setup

 

Setpoint

1400

Alarm Type

PV2 proc high

Hysteresis

1

Smart Alarm

Disabled

ON Delay Time (sec)

0

Relay Assignments

 

Relay 1

Event 0

Relay 2

Event 1

Relay 3

Event 2

Relay 4

Event 3

Relay 5

Event 4

Relay 6

Event 5

Relay 7

Event 6

Relay 8

Program, alm1, flow dev

Relay Setpoints

 

Relay ON SP for IN1 A

0

Relay OFF SP for IN1 A

0

Relay ON SP for IN1 B

0

Relay OFF SP for IN1 B

0

Relay ON SP for IN1 C

0

Relay OFF SP for IN1 C

0

Relay ON SP for IN2 A

0

Relay OFF SP for IN2 A

0

Relay ON SP for IN2 B

0

Relay OFF SP for IN2 B

0

Relay ON SP for IN2 C

0

Relay OFF SP for IN2 C

0

Relay ON SP for IN3 A

0

Relay OFF SP for IN3 A

0

Relay ON SP for IN3 B

0

Relay OFF SP for IN3 B

0

Relay ON SP for IN3 C

0

Relay OFF SP for IN3 C

0

Input 1 Setup

 

Input type

K

Filter time

0

Initial scale

0

Full scale

10000

Decimal Point location

0

Open TC

Up scale

Input offset

0

Trip point 1 setpoint

0

Trip point 1 force value

0

Trip point 1 direction

Input above setpoint

Trip point 2 setpoint

0

Trip point 2 force value

0

Trip point 2 direction

Input above setpoint

High input limit setpoint

-32768

High input limit hysteresis

-32768

Input 2 Setup

 

Input type

4-20 mA

Filter time

0

Initial scale

-27.99

Full scale

28.00

Decimal Point location

2

Open TC

Up scale

Input offset

0.00

Trip point 1 setpoint

0.00

Trip point 1 force value

0.00

Trip point 1 direction

Input above setpoint

Trip point 2 setpoint

0.00

Trip point 2 force value

0.00

Trip point 2 direction

Input above setpoint

High input limit setpoint

-327.68

High input limit hysteresis

-327.68

Input 3 Setup

 

Input type

K

Filter time

0

Initial scale

0

Full scale

10000

Decimal Point location

0

Open TC

Up scale

Input offset

0

Trip point 1 setpoint

0

Trip point 1 force value

0

Trip point 1 direction

Input above setpoint

Trip point 2 setpoint

0

Trip point 2 force value

0

Trip point 2 direction

Input above setpoint

High input limit setpoint

-32768

High input limit hysteresis

-32768

Output 1 Setup

 

Assignment

Loop 3 inc

Offset

0

Range

100

Current selection

4-20 mA

Output 2 Setup

 

Assignment

Loop 2 inc

Offset

0

Range

100

Current selection

4-20 mA

Passcodes

 

Level 1 code

1

Level 2 code

2

Web level 1 code

111

Web level 2 code

222

Web change enable

1

Programmer alarm

Normally open

Alarm 1

Normally open

Alarm 2

Normally open

Alarm 3

Normally open

IP Address

 

IP Address

192.168.1.200

IP Mask

255.255.255.0

IP Gateway

192.168.1.1

Event Control

 

Hold instrument number

0

Hold minimum PV

0

Hold maximum PV

2000

Event for program run

-1

Event for program reset

-1

Event 0

 

Event 1

 

Event 2

 

Event 3

 

Event 4

 

Event 5

 

Event 6

 

Event 7

 

Event 8

 

Event 9

 

Event 10

 

Event 11

 

Event 12

 

Event 13

 

Event 14

 

Event 15

 

Valve Setup

 

Control mode

Individual trim

DA switch point

60

Auto valve event

No

Valve 1 Input

 

Zero scale

0

Full scale

300

Trim enable

No

Target setpoint

150

Trim range

0

Zero SP scale

0

Full SP scale

300

Valve max

300

Deviation setpoint

20

Dev. Alarm delay (sec)

300

Gas type

Nitrogen

Valve decimal place

0

Valve 2 Input

 

Zero scale

0

Full scale

300

Trim enable

Yes

Target setpoint

150

Trim range

50

Zero SP scale

0

Full SP scale

300

Valve max

300

Deviation setpoint

60

Dev. Alarm delay (sec)

60

Gas type

Ammonia

Valve decimal place

0

Valve 3 Input

 

Zero scale

0

Full scale

150

Trim enable

No

Target setpoint

10

Trim range

25

Zero SP scale

0

Full SP scale

150

Valve max

150

Deviation setpoint

10

Dev. Alarm delay (sec)

300

Gas type

Dissociated Ammonia

Valve decimal place

0

Valve 4 Input

 

Zero scale

0

Full scale

0

Trim enable

No

Target setpoint

0

Trim range

0

Zero SP scale

0

Full SP scale

0

Valve max

0

Deviation setpoint

Off

Dev. Alarm delay (sec)

0

Gas type

Hydrogen

Valve decimal place

0