ADAM Module Offset Correction
The ADAM Module Offset Correction menu option gives the user the ability to offset any input (1-40) on any ADAM.
Enable Offsets for SSi AIB (Analog Input Board)
This option will allow the user to enable offsets to be used for inputs on an SSi analog input board. The options are Yes or No.
Input 1 – 40
The offset can be in degrees + or –, and it is typically used to compensate for incorrect T/C wires. Clicking on any of the values will display an input box from which the user can select a new offset. The range is –50.0 to 50.0.
Input 0 Correction – Input 39 Correction
The user can also use a curve (set up in Curve Entry section) to apply as a correction to each of the inputs. Note: The inputs are labeled 1 to 40, but the input corrections are labeled 0 to 39, so Input Correction 0 is for Input 1, etc.