Load T/C Configuration


Configuration of any Load TCs must be completed under this menu item.

 

IMPORTANT!

 

It should also be noted that not all analog inputs on SRs to a 9205 will be load thermocouples. They are often used as a means to capture other data. Care MUST be taken with selecting which is a Load TC and which is not, as improperly selecting something that is not a Load TC may cause the program to run excessively long or not run long enough.

 

 

Load TC Enable

This value will manually toggle between on, on + alarms, and off.

On – T/C Enabled

On + Alarms – T/C Enabled, Programmer alarm114 provided if out of band (Default wait limits)

Off – T/C not enabled

 

Control TC

This value allows the user to set the TC to be part of the group of Load TCs that can hold the program if it is out of band.  The values are active or not active (shown as blank).

 

TC 1 – 27

This value allows the user to manually turn the T/C from active to not active to be part of the group of TCs that can hold the program if it is out of band.

 

Input 1 – 3

This value allows the user to assign analog inputs 1, 2, and 3 as Load TCs by selecting the active state for each input. (Not active means that the input is not set up as a Load TC.)

 

Load T/C Alm On Delay (Sec)

This option will allow the user to set a delay time, in seconds, before the load T/C alarm is activated.  The range is 032767.

 

The Return button will return the user to the menu screen.