Aux Setpoint Configuration
See the menu option Client Instrument Setup for configuration prior to using Aux Setpoint Configuration. Aux Set Point Configuration is an automatic set point retransmission with a corresponding custom offset and delay to one or more of the first 3 configured Client instruments. The delay is in minutes and is only active when the set point is dropped. This feature would most commonly be used to keep the alarm set point of an overtemp tracking the furnace's main set point (with offset). The delay allows the furnace time to cool below the level specified so that there is no overtemp alarm when the furnace is cooling.
Retrans to Client 1 – Retrans to Client 3
This option will determine which control loop to use as the retransmission value.
The options are:
Off
Loop 1
Note – If the setpoint is 0, then the retransmission is blocked.
Setpoint Offset Sl 1 – Setpoint Offset Sl 3
Values entered will take the decimal point of the PV into account, but each value is entered in whole numbers:
Carbon: 1 = 0.01
Temperature: 1 = 1
This option will apply the offset when retransmitting the value from the control loop. The range is –32768 to 32767.
Setpoint Delay Sl 1 – Setpoint Delay Sl 3
This is measured in seconds. This option will set the number of seconds to delay before retransmitting the value from the control loop. The range is –32768 to 32767.