Analog Output Setup

Analog Output Setup
The 9205 controller has the option of six analog outputs. The outputs are ranged for a 4 – 20 milliamp signal or a 0 – 20 milliamp signal. Each output comes with a factory default configuration dependent on the application. Each output can be modified prior to shipment to your facility or in the field by a supervisor.

 

Analog Output Terminals

Analog output 1 – terminals 24 and 25

Analog output 2 – terminals 25 and 26

Analog outputs 3, 4, 5, and 6 are enabled by use of an SSi QuadDAC board that connects to two RS485 terminals on the 9205 (terminals 5 and 6 for Client 1, terminals 22 and 23 for Client 2). Use the Load T/C Configuration

 

menu to configure communication parameters.

 

Assignment

The analog output assignment can be modified depending on your system requirements. To change the Assignment first select which analog output you want to change by selecting it in the pull-down menu at the top of the screen.  The following is a list of the options:

 

PV 1 retrans

Loop 1 inc

Loop 1 dec

Loop 1 combo

PV 2 retrans

Loop 2 inc

Loop 2 dec

Loop 3 combo

PV 3 retrans

Loop 3 inc

Loop 3 dec

Loop 3 combo

Input 1 retrans

Input 2 retrans

Input 3 retrans

Not assigned

O2 offset log

SP1 retrans

SP2 retrans

SP3 retrans

Programmer ID number

Programmer Valve 1 SP

Programmer Valve 2 SP

Programmer Valve 3 SP

Programmer Valve 4 SP

Prog 1 Quench speed (0-1000=0-100%)

Programmer DAC 1

Programmer DAC 2

Programmer DAC 3

Programmer DAC 4

Programmer DAC 5

Programmer DAC 6

Prog 2 Quench speed (0-1000=0-100%)

Programmer 2 DAC 1

Programmer 2 DAC 2

Programmer 2 DAC 3

Programmer 2 DAC 4

Programmer 2 DAC 5

Programmer 2 DAC 6

Programmer 2 ID number

Programmer 2 Valve 1 SP

Programmer 2 Valve 2 SP

Programmer 2 Valve 3 SP

Programmer 2 Valve 4 SP

Disabled

 

Offset

This is the starting point, the Process Variable value at which you get 4 milliamps if the output is set up as 4-20mA (or 0 milliamps if output is set up as 0-20mA).  Clicking on this value will display an input box from which the user can select a new value.  The range is –32768 to 32767.

 

Range

This is a Process Variable value between 4 and 20 milliamps (or 0 and 20 milliamps, depending on setup).  Clicking on this value will display an input box from which the user can select a new value.  The range is
–32768 to 32767.

Note - The range, although not displayed with a decimal point, contains a decimal point that is dependent on the process variable selected. For example, if the offset is 20 mV for 4 mA, and you want 100 mV to be 20 mA, then your range should be 80. If the process variable is temperature, then the range will be 80, since temperature PVs do not have a decimal. If the PV is % Carbon, then the range will need to include the two decimal points for % Carbon. So, a range of 80 will be entered as 8000. See below for more examples.

 

Current Selection 

Provides the option of 4-20 mA or 0-20 mA control.  Clicking on this value will display an input box with a drop-down list from which the user can select either of the two values listed above.

 

Offset and Range when assigned to a control loop

Inc : 0 = 4mA, 100 = 20mA

Dec : 0 = 4mA, -100 = 20mA

 

Example: if 4 – 20 mA = 800 mV  - 1200 mV

    Offset  = 800 (starting point)

    Range = 400

 

The Return button will return the user to the menu screen.