Wait

 

When using the option wait with a set point Opcode, the recipe will not advance to the next step until the PV value falls within the wait limit band. The wait limit band is defined as Set Point plus/minus the active tolerance. The active tolerance begins each recipe as the value defined as the default wait limit; this can be changed using the SET_WAIT opcode.

 

 

 

 

For example, assume a Set Point of 1500° and a wait limit of 15°. Using the SETPT opcode paired with a wait option, the recipe will not advance until the temperature PV is between 1485°-1515°.