TC Extension Correction Curves

TC Extension Correction Curves Menu
This menu option will allow the user to set up to three TC correction curves for the 9130 controller.  Clicking on the “click” value for a curve will display the curve edit form.  Note: If the first “Temperature” value and the first “Error” value are both zero, then the curve will not be set.  The user can enter up to ten “Temperature”/“Error” combinations.  The range for the “Temperature” field is –300 to 9999.  The range for the “Error” field is –30.000 to 30.000.

TC Extension Correction Curves Menu - Curve Edit

NOTE: Curves are interpolated between points in order to provide
a smooth transition between those points.  For example:

 

Point

Temp

Error

1

100

0

2

300

2

 

In the above setup, temperatures would read as follows:

 

Actual Temperature

Displayed

Temperature

100

100

150

150.5

200

201

250

251.5

300

302