Relay Assignments
The 9130 controller has the option of using eight relay outputs. All of the relays have a positive common terminal and independent negative terminals. All of the relays are configured in a normally closed position except relay number eight, which has both a normally closed (NC) and a normally open (NO) terminal. These relays can be configured to work with events, alarms, loops, burnoff and alarm combinations.
Relay Output Terminals
Relay Output 1 – terminals 7 and 8
Relay Output 2 – terminals 7 and 9
Relay Output 3 – terminals 7 and 10
Relay Output 4 – terminals 7 and 11
Relay Output 5 – terminals 7 and 12
Relay Output 6 – terminals 7 and 13
Relay Output 7 – terminals 7 and 14
Relay Output 8 – terminals 7 and 15 NC
Relay Output 8 – terminals 7 and 16 NO
Relay Output Choices
Loop 1 fwd Event 6
Loop 1 rev Event 7
N/A Event 8
N/A Event 9
N/A Event 10
N/A Event 11
Programmer Alarm Event 12
Alarm 1 Event 13
Alarm 2 Event 14
Alarm 3 Event 15
Event 0 TC Redundancy Select (OFF = TC 1; ON = TC 2)
Event 1 PV Switching Select (OFF = PV 1; ON = PV 2)
Event 2 Timer Running
Event 3 Timer Complete
Event 4 Load TC Deactivated
Event 5 Alarm Combination
N/A
The “Alarm Combination” option will allow the user to select the specific combination of alarms to use.