Relay Assignments

Relay Assignments Menu
The 9130 controller has the option of using eight relay outputs. All of the relays have a positive common terminal and independent negative terminals. All of the relays are configured in a normally closed position except relay number eight, which has both a normally closed (NC) and a normally open (NO) terminal.  These relays can be configured to work with events, alarms, loops, burnoff and alarm combinations.

 

Relay Output Terminals

Relay Output 1 – terminals 7 and 8

Relay Output 2 – terminals 7 and 9

Relay Output 3 – terminals 7 and 10

Relay Output 4 – terminals 7 and 11


Relay Output 5 – terminals 7 and 12

Relay Output 6 – terminals 7 and 13

Relay Output 7 – terminals 7 and 14

Relay Output 8 – terminals 7 and 15 NC

Relay Output 8 – terminals 7 and 16 NO

 

Relay Output Choices

Loop 1 fwd        Event 6            

Loop 1 rev        Event 7

N/A            Event 8

N/A            Event 9        

N/A            Event 10        

N/A            Event 11        

Programmer Alarm    Event 12                

Alarm 1        Event 13

Alarm 2        Event 14

Alarm 3        Event 15

Event 0        TC Redundancy Select (OFF = TC 1; ON = TC 2)

Event 1        PV Switching Select (OFF = PV 1; ON = PV 2)

Event 2        Timer Running

Event 3        Timer Complete

Event 4        Load TC Deactivated

Event 5        Alarm Combination

N/A

 

 

The “Alarm Combination” option will allow the user to select the specific combination of alarms to use.