Aux Setpoint Configuration
See the menu option Client Instrument Setup for configuration prior to using Aux Setpoint Configuration. This menu option allows for up to 3 Client instruments to have the setpoint retransmitted from one of the control loops. This menu option is typically used to retransmit an alarm setpoint value to an overtemp controller.
Retrans to Client 1 – Retrans to Client 3
This option will determine which control loop to use as the retransmission value.
The options are:
Off
Loop 1
Note – If the setpoint is 0, then the retrans is blocked.
Setpoint Offset Sl 1 – Setpoint Offset Sl 3
Values entered will take the decimal point of the PV into account, but each value is entered in whole numbers:
Carbon: 1 = 0.01
Temperature: 1 = 1
This option will apply the offset when retransmitting the value from the control loop. The range is –32768 to 32767.
Setpoint Delay Sl 1 – Setpoint Delay Sl 3
This is measured in seconds. This option will set the number of seconds to delay before retransmitting the value from the control loop. The range is –32768 to 32767.