Furnace Setup

The Furnace Setup menu option is an administrative access only option.  Do not make any adjustments on the screen without first contacting Super Systems, Inc. at (513) 772-0060.

 

PVT Type

There are nine PVT choices for the 9125:

 

%Carbon            Cascade

Dew Point            % Carbon + Redundant TC

Millivolts            Dew Point + Redundant TC

Multiloop            Millivolts + Redundant TC

% Carbon + Dual Temp

 

%Carbon:  Process variable will calculate for carbon potential along with a temperature loop.  Loop 1 is based off of Input 1 (terminals 31, 32 probe sensor millivolts) and Input 2 (terminals 29, 30 probe TC).  These two inputs together constitute loop 1.  Loop 2 comes from Input 3 (terminals 27, 28) which is temperature control.

 

Cascade:  Three loops of temperature control work together in a cascade setting.

 

Dew Point:  Control will be for dew point along with a temperature loop.  Loop 1 is based off of Input 1 (terminals 31, 32 probe sensor millivolts) and Input 2 (terminals  29, 30 probe TC).  These two inputs together constitute loop 1.  Loop 2 comes from Input 3 (terminals 27, 28) which is temperature control.

 

%Carbon + Redundant TC:  This functions the same way as the %Carbon option with an additional thermocouple for Loop 3.  The two thermocouples are used to control carbon, and the operator can choose the setting that will be used. 

 

Millivolts:  Control is based off of what the millivolt reading is and also reads temperature.

 

Dew Point + Redundant TC:  This functions the same way as the Dew Point option with an additional thermocouple for Loop 3.  The two thermocouples are used to control dew point, and the operator can choose the setting that will be used. 

 

Multiloop:  Three loops of control can be assigned as selected.

 

Millivolts + Redundant TC:  Control is based off of the millivolt reading and also reads temperature.  Loop 3 is another thermocouple.

 

%Carbon + Dual Temp:  This functions similarly to %Carbon.  Input 2 is the control TC.  IT is not used to calculate carbon potential with input one and to control furnace temperature.  Input 3 in the third loop and is another TC. 

 

IMPORTANT: If the 9125 is controlling % Carbon or Dew Point, control will be disabled if either or both of the following are true:

  • Millivolts registered by probe are below 500 mV or above 1300 mV.

  • Temperature registered by probe is below 900°F or above 2100°F.

 

Temperature Mode

This allows the operator to choose either degrees Fahrenheit or degrees Celsius for the temperature.  The options are °C or °F.  Pressing OK will set the choice.

 

Loop 1 Instrument

 

Loop 1 (typical)        Instrument 5        Instrument 12        Instrument 19

Loop 2            Instrument 6        Instrument 13        Instrument 20

Loop 3            Instrument 7        Instrument 14        Instrument 21

Instrument 1        Instrument 8        Instrument 15        Instrument 22

Instrument 2        Instrument 9        Instrument 16        Instrument 23

Instrument 3        Instrument 10        Instrument 17        Instrument 24

Instrument 4        Instrument 11        Instrument 18        Instrument 25

 

Loop 2 Instrument

 

Loop 1            Instrument 5        Instrument 12        Instrument 19

Loop 2 (typical)        Instrument 6        Instrument 13        Instrument 20

Loop 3            Instrument 7        Instrument 14        Instrument 21

Instrument 1        Instrument 8        Instrument 15        Instrument 22

Instrument 2        Instrument 9        Instrument 16        Instrument 23

Instrument 3        Instrument 10        Instrument 17        Instrument 24

Instrument 4        Instrument 11        Instrument 18        Instrument 25

 

Event Instrument

Allows for a client instrument (or internal) to be the defined event control device.  The types of instruments are:  Internal, Instrument 1Instrument 25. Internal is typical.

 

Date and Time

This value is the current date and time on the 9125 controller only (not the local computer or the touch screen, if applicable).  The time on the controller is displayed in the 24-hour format, so 8 = 8 AM, and 14 = 2 PM.  Note: The date and time of the touch screen can be changed (if necessary) by selecting the date and time in the lower right corner on the touch screen, once the screen software has been shut down and the Windows™ desktop is visible.  Then, at the CE screen the date and time can be changed by double taping the time in the bottom right corner and setting it, then select “apply”. For this to take effect the screen needs to be rebooted; on the older TPC 642 displays the registry needs to be saved under TPC Configuration icon, the Misc Tab and then reboot the touch screen. The date and time that is recorded on the flash card (and therefore the datalog data) is the date and time of the Advantech display, not the controller.

 

Deviation Alarm Delay

This value is the delay for the alarm if a deviation alarm is detected.  The range is 0 to 10000.

 

Name

This will allow the user to give the controller a display name.

 

PV1 Name

This will allow the user to give the first process variable a display name.

 

PV2 Name

This will allow the user to give the second process variable a display name

 

PV3 Name

This will allow the user to give the third process variable a display name

 

Cascade Inhibit

Note: This field is only applicable if the controller is in Cascade mode.  This will turn cascade control on or off.  When inhibit = enabled, the 9125 functions as a multi-loop controller with three control loops.  The options are: enabled or disabled.

 

PV Difference Cutback

Note: This field is only applicable if the controller is in Cascade Mode.  This is used with the Cascade Lower Range EOPV and Cascade Upper Range EOPV to limit the absolute % output of the furnace loop.  This will turn the PV difference cutback feature on or off.  The options are: enabled or disabled.

    

Cascade Lower Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode.  This is the cascade lower range end of PV difference.  This is used with the PV Difference Cutback and Cascade Upper Range EOPV to limit the absolute % output of the furnace loop.  Between the lower range EPOV and the upper range EOPV, there is a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum % output for the furnace loop.  The range is -300 to 10000.

 

Cascade Upper Range EOPV

Note: This field is only applicable if the controller is in Cascade Mode.  This is the cascade upper range end of PV difference.  This is used with the Cascade Lower Range EOPV and PV Difference Cutback to limit the absolute % output of the furnace loop.  Between the lower range EPOV and the upper range EOPV, there is a linear interpolation from 0 to the loop 2 output maximum (usually 100 %) that determines the maximum % output for the furnace loop.  The range is -300 to 10000.

 

Example: With the Lower EOPV set to 10 and the Upper EOPV set to 110, if the load PV is 1700 and the furnace PV is 1710, the full 100% output is available.  If the load PV is 1600 and the furnace PV is 1710, the furnace output will not go above 0%.  If the load PV is 1655 and the furnace PV is 1710, the maximum output for the furnace loop will be limited to 55%: (1710 – 1655)/(110-10) * (1.0).

 

Multiloop Display

This option allows the user to decide which combination of loops will be displayed on the default status screen.  The choices are:

No display    Loop 1, Loop 2        Loop 2, Loop 3    

Loop 1        Loop 3            Loop 1, Loop 2, Loop 3

Loop 2        Loop 1, Loop 3

 

The Return button will return the user to the menu screen.