Temperature Instruments
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Series 20 |
11 |
123 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
30 |
138 |
1 |
1 |
Temperature Controller Setpoint |
|
18 |
130 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Yokogawa 750 |
2 |
2 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
3 |
100 |
1 |
1 |
Temperature Controller Setpoint |
|
4 |
4 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
UDC 3300’s |
1 |
0 |
10 |
10 |
Temperature Controller Actual |
(Modbus Mode) |
3 |
2 |
10 |
10 |
Temperature Controller Setpoint |
|
4 |
3 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Dualpro Loop 1 |
18 |
17 |
8 |
8 |
Temperature Controller Actual |
(Modbus Mode) |
7 |
6 |
1 |
1 |
Temperature Controller Setpoint |
|
41 |
40 |
41 |
41 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Dualpro Loop 2 |
18 |
17 |
8 |
8 |
Temperature Controller Actual |
(Modbus Mode) |
8 |
7 |
1 |
1 |
Temperature Controller Setpoint |
|
42 |
41 |
41 |
41 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Dualpro Loop 1 |
17 |
17 |
8 |
8 |
Temperature Controller Actual |
(MMI Mode) |
6 |
6 |
1 |
1 |
Temperature Controller Setpoint |
|
40 |
40 |
41 |
41 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Dualpro Loop 2 |
17 |
17 |
8 |
8 |
Temperature Controller Actual |
(MMI Mode) |
7 |
7 |
1 |
1 |
Temperature Controller Setpoint |
|
41 |
41 |
41 |
41 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Eurotherm 2404 |
1 |
1 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
2 |
2 |
1 |
1 |
Temperature Controller Setpoint |
|
3 |
3 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Eurotherm 2500 |
26 |
1025 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
27 |
1026 |
1 |
1 |
Temperature Controller Setpoint |
Assumes Loop 2 is Temperature |
29 |
1028 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Unipro 3.5 |
3 |
25 |
8 |
8 |
Temperature Controller Actual |
(MMI Mode) |
1 |
1 |
1 |
1 |
Temperature Controller Setpoint |
|
5 |
118 |
1 |
1 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Unipro 3.0 |
3 |
25 |
8 |
8 |
Temperature Controller Actual |
(MMI Mode) |
1 |
1 |
1 |
1 |
Temperature Controller Setpoint |
|
5 |
118 |
1 |
1 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Carbpro 3.5 Slave |
9 |
46 |
1 |
1 |
Temperature Controller Actual |
(MMI Mode) |
3 |
18 |
1 |
1 |
Temperature Controller Setpoint |
|
12 |
53 |
41 |
41 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Carbpro 3.0 Slave |
9 |
46 |
1 |
1 |
Temperature Controller Actual |
(MMI Mode) |
3 |
18 |
1 |
1 |
Temperature Controller Setpoint |
|
12 |
53 |
41 |
41 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
10Pro Slave or E Slave |
2 |
2 |
1 |
1 |
Temperature Controller Actual |
(MMI Mode) |
3 |
3 |
1 |
1 |
Temperature Controller Setpoint |
|
4 |
4 |
1 |
1 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Dualpro Input C |
19 |
19 |
8 |
8 |
PV |
|
5 |
5 |
1 |
1 |
Setpoint Loop 1 |
|
40 |
40 |
41 |
41 |
Percent Output Loop 1 |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Series 9200 Loop 1 |
3 |
126 |
1 |
1 |
Temperature Controller Actual |
|
5 |
128 |
1 |
1 |
Temperature Controller Setpoint |
|
7 |
130 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Series 9200 Loop 2 |
8 |
131 |
1 |
1 |
Temperature Controller Actual |
|
10 |
133 |
1 |
1 |
Temperature Controller Setpoint |
|
12 |
135 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Series 9200 Loop 3 |
13 |
136 |
1 |
1 |
Temperature Controller Actual |
|
15 |
138 |
1 |
1 |
Temperature Controller Setpoint |
|
17 |
140 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Series 9100 Loop 2 |
1 |
104 |
1 |
1 |
Temperature Controller Actual |
|
36 |
139 |
1 |
1 |
Temperature Controller Setpoint |
|
28 |
131 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Eurotherm Loop 1 |
1 |
1 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
2 |
2 |
1 |
1 |
Temperature Controller Setpoint |
|
3 |
3 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Eurotherm Loop 2 |
26 |
1025 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
27 |
1026 |
1 |
1 |
Temperature Controller Setpoint |
|
29 |
1028 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Eurotherm Loop 3 |
51 |
1049 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
52 |
1050 |
1 |
1 |
Temperature Controller Setpoint |
|
53 |
1052 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
9500 Valve Controller Valve 1 |
30 |
130 |
1 |
1 |
Flow Actual |
|
56 |
156 |
1 |
1 |
Flow Setpoint |
|
54 |
154 |
1 |
1 |
Flow Percent of Full Scale |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
9500 Valve Controller Valve 2 |
31 |
131 |
1 |
1 |
Flow Actual |
|
66 |
166 |
1 |
1 |
Flow Setpoint |
|
64 |
164 |
1 |
1 |
Flow Percent of Full Scale |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
9500 Valve Controller Valve 3 |
32 |
132 |
1 |
1 |
Flow Actual |
|
76 |
176 |
1 |
1 |
Flow Setpoint |
|
74 |
174 |
1 |
1 |
Flow Percent of Full Scale |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
9500 Valve Controller Valve 4 |
33 |
133 |
1 |
1 |
Flow Actual |
|
86 |
186 |
1 |
1 |
Flow Setpoint |
|
84 |
184 |
1 |
1 |
Flow Percent of Full Scale |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
SSi 7SL Limit Controller |
4 |
123 |
1 |
1 |
Limit Controller Actual |
|
8 |
177 |
1 |
1 |
Limit Controller Alarm Threshold (SP) |
|
11 |
310 |
1 |
1 |
Limit Controller Main Setpoint |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Flow Meter |
1 |
16 |
1 |
1 |
Flow |
|
3 |
18 |
1 |
1 |
Setpoint |
|
0 |
0 |
1 |
1 |
No Value Available |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
UMC 800 Loop 1 |
0 |
64 |
1 |
1 |
PV Actual |
All Values are |
4 |
68 |
1 |
1 |
Working Setpoint |
Floating Point |
6 |
70 |
1 |
1 |
Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
SSi Quad DAC Ch. 0 |
10 |
10 |
1 |
1 |
DAC Out |
|
10 |
10 |
1 |
1 |
DAC Out |
|
16 |
16 |
1 |
1 |
No Value Available |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
SSi Quad DAC Ch. 1 |
11 |
11 |
1 |
1 |
DAC Out |
|
11 |
11 |
1 |
1 |
DAC Out |
|
16 |
16 |
1 |
1 |
No Value Available |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
SSi Quad DAC Ch. 2 |
12 |
12 |
1 |
1 |
DAC Out |
|
12 |
12 |
1 |
1 |
DAC Out |
|
16 |
16 |
1 |
1 |
No Value Available |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
SSi Quad DAC Ch. 3 |
13 |
13 |
1 |
1 |
DAC Out |
|
13 |
13 |
1 |
1 |
DAC Out |
|
16 |
16 |
1 |
1 |
No Value Available |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Yokogawa UT350/320 |
2 |
2 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
3 |
300 |
1 |
1 |
Temperature Controller Setpoint |
|
4 |
4 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Yokogawa UP750/550 Loop 2 |
18 |
18 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
19 |
101 |
1 |
1 |
Temperature Controller Setpoint |
|
20 |
20 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Yokogawa UP350 |
2 |
2 |
1 |
1 |
Temperature Controller Actual |
(Modbus Mode) |
3 |
138 |
1 |
1 |
Temperature Controller Setpoint |
|
4 |
4 |
10 |
10 |
Temperature Controller Percent Output |
Controller |
Source Location |
Write Register |
Read Scale |
Write Scale |
Description |
Honeywell DCP551 |
4 |
259 |
10 |
10 |
Temperature Controller Actual |
|
5 |
702 |
10 |
10 |
Temperature Controller Setpoint |
|
0 |
0 |
10 |
10 |
Temperature Controller Percent Output |